9 Inspection and maintenance
24
Installation and maintenance instructions Energy 0020201109_01
1
2
1.
Detach the siphon
(2)
.
2.
Clean the lower section of the siphon with clean water.
3.
Disconnect the condensate line
(1)
.
4.
Refit the unit and make sure that the seals are fitted
correctly.
5.
Fill the lower section of the siphon with water.
–
Distance between the edge of the condensate si-
phon and the water: 10 mm
6.
Screw in the siphon tightly.
9.11
Combustion unit
9.11.1 Checking the ignition and flame control
electrode
1
2
3
4
5
1.
Remove the air intake pipe. (
→
Page 22)
2.
Disconnect the connection
(2)
and the earthing cable
(1)
.
3.
Remove the fixing screws
(3)
.
4.
Carefully remove the electrode from the combustion
chamber.
5.
Check whether the ends of the electrodes
(5)
are free
from damage.
6.
Clean and check the gap between the electrodes.
–
Distance between the ignition and flame control
electrodes: 3.5 … 4.5 mm
7.
Make sure that the seal
(4)
is free from damage.
▽
If necessary, replace the seal.
9.11.2 Removing the gas-air mixture unit
Note
The gas-air mixture unit consists of three main
components:
–
Ventilator
–
Gas valve,
–
Burner door
2
1
3
4
5
1.
Remove the gas spigots
(2)
.
2.
Remove the plugs
(1)
and
(3)
.
3.
Loosen the nuts
(5)
.
4.
Remove the burner unit from the boiler casing
(4)
.
5.
Check whether the bolts on the boiler casing are free
from damage.
▽
Replace the boiler casing if necessary.
6.
Check whether the insulation on the burner valve is free
from damage.
▽
Replace the burner valve if necessary.