GETTING THE PANEL RUNNING
Apply AC power to the Panel.
The LCD should display the software version and the message ‘INITIALIZING’. This will be followed by the date
and time (and the company name if it has been set). Within a few seconds faults will be reported, these will
overwrite the date and time (and company name).
The SYSTEM ON LED on the fascia of the panel should be flashing green. This indicates that the system is in
Installation Mode. If the LED is solid green the system is in Active Mode and needs to be put into Installation
Mode - refer to the programming section for details on how to do this.
If the SYSTEM ON LED is flashing and information is being displayed on the LCD then the Panel is functional.
If the SYSTEM FAULT LED is lit and a continuous tone is audible then remove power and confirm that the SIM
CARD is fitted correctly.
GETTING A REPEATER RUNNING
The supply to the repeater is obtained directly from the auxiliary power supply output on the panel.
Apply power to the repeater.
If the panel is powered up and the data loop connections between panel and repeater(s) are properly made,
the information shown on the LCD display as well as the LED indicator status from the panel will replicate
itself on the repeater.
Press the SYSTEM RESET switch and you should see on the LCD display the message "JUNIOR" as well as the
software version number, followed by the word, "INITIALIZING".
If after a few seconds upon completion of the initialization phase the LCD display shows the message, "NO
COMMS TO PANEL" and the FAULT Led is lit-up, verify the condition of the panel. If it is powered up and
working properly then verify the data loop connections.
If the SYSTEM FAULT LED is lit and a continuous tone is audible then remove power and confirm that the SIM
CARD is fitted correctly.