Zones - Disable & Assign
All the functions associated with managing Zones
3-1 Disable Zones
Allows you to disable or enable Zones.
All devices in disabled Zones will cease to operate with the exception of the (audible) output from loop
sounders.
Any Zones that are disabled will also be indicated when programming mode is exited. They can then be
reviewed using the DISABLED (QUEUE REVIEW) button.
3-2 Assign Sounder Groups to Zones
Sounder Groups (set up using the Sounders programming functions) can be assigned to Zones.
Each Zone can be assigned two sounder groups. The first Sounder Group is activated when the first fire is
detected, the second Sounder Group is activated when a second fire is detected in the same Zone.
3-3 Assign I/O Groups to Zones
I/O Groups (set up using the I/O programming functions) can be assigned to Zones.
The first 4 I/O groups are activated when the first fire is detected, the 5th I/O group is activated when a second
fire is detected in the same Zone.
The details of the activation are set up using the I/O programming functions.
3-4 Assign Zone to Device
Allows the detection Zone to be defined.
Select which devices make up which Zones. If a device has a text label it will be displayed. If a Zone has a text
label it will also be displayed.
Up to 384 Zones can be defined.
Zone 000 is not a Zone and indicates no Zone has been assigned.
3-5 Zone Sounder Delay Set-up
Allows the sounder activation delay to be enabled or disabled for each specific Zone.
Note that this delay will only occur if the following has also been set:
• Sounder programming function 4-6: The sounder delay period is set, the delay is set to ZONAL MODE and
the devices that initiate the delay have been specified.
• The front panel ACTIVE DELAYS button has been set to on (LED lit).
NOTE: Specific devices in the Zone can be set to override this delay.