Voltage
EMC Standard
EN55022 class B
EN61000-4-2,3,4,5,6,8,11
EN61000-3-2,3
Current
2.4A PSU’s recommended for 1 and 2 loop panels.
The maximum alarm sounder current is 450mA for both conventional sounder circuits.
The maximum quiescent current per loop is 340 mA. The loop short circuit (trip) current is 900mA.
Battery
Internal maximum 24V / 7AH
Primary supply voltage
230 V +10% / -15% V AC
POWER REQUIREMENTS
NEUTRAL
LIVE
MEANWELL
DANGER
230 VOLTS
MODEL: PS-65-27
EARTH
POWER SUPPLY SPECIFICATION - MEANWELL Model: PS-65-27
MAINS SUPPLY VOLTAGE
INTERNAL POWER SUPPLY
TOTAL OUTPUT CURRENT
SUPPLY AND BATTERY CHARGER MONITORED?
BATTERIES MONITORED
MAX BATTERY SIZE
MAINS FUSE
BATTERY FUSE
MAX CURRENT DRAW FROM BATTERY (MAINS FAIL)
230 V +10%/ -15% V AC
Min. 20 V DC - Max. 30 V DC
(28.5 V DC nominal) Max. Ripple 1 V peak-peak
1.7A @ 230 Vac
YES
YES
2 x 12 V 7 AH VRLA
4 A - 250 V Slow Blow - 20 mm
1.85 Amp Resettable - Electronic Fuse
1.5 Amp Max. @ Max. Operating Temperature
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015
JUNIOR V4-L
- FIRE ALARM CONTROL PANEL