5-4 Inhibit I/O for Device
Allows a device to be set so that it does not operate certain I/O Groups.
The options are:
COMMON
The Common I/O Group (512) is not activated when the device detects fire
ZONAL
The Zone I/O Group for the device is not activated when the device detects fire
ALL
No I/O Groups are activated when the device detects fire
COMMON or ZONAL inhibits will not inhibit the I/O Group directly assigned to a device (function 5-3 Assign
I/O Group to Device) if that device detects fire.
Allows you to define how an I/O module will perform when an evacuate is signaled. By default an I/O module
will not activate unless it has been assigned to an I/O Group than has been activated.
Allows a specific I/O module to be set so that it activates immediately even if the rest of the I/O is set to be
activated after a delay.
Allows the I/O (output) delay to be set. This delay applies to all I/O module outputs.
The maximum delay that is allowed is 10 minutes.
There is only one I/O timer so once it has expired events activating further delayed I/O groups will cause
immediate I/O operation.
5-5 I/O Unit Action upon Evacuate
5-6 I/O Unit Delay or Immediate
5-7 I/O Delay Set-up
NOTE:
Delays will only occur if front panel ACTIVE DELAYS button has been set to on.
Specific I/O modules (function 5-6) and specific detectors (function 6-1-6) can be set to override
this delay.
NOTE: An evacuate is not considered as an automatically detected fire event.
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015
JUNIOR V4-L
- FIRE ALARM CONTROL PANEL