Global Power Technologies
INSTALLATION
05585 rev11 | Model 8550-SD
Page 12 of 53
c) From the factory altitude marked on the curve, measure the amount of pressure that
adjustment is required for your site’s altitude by counting vertically from the Factory
Elevation mark at 0 psi/kPa. Enter this number on the Start-up Data Sheet.
For example:
If your TEG will be installed at a site with an altitude of
2460
ft (
750
m), increase your
burner fuel pressure by 2.61 psi (18 kPa) from the factory setting.
Figure 7 – Altitude Adjustment