Global Power Technologies
1120 - Class I, Division 2, Group D, T3
FIELD TROUBLE SHOOTING
SYMPTOMS
CAUSE AND/OR REMEDY
Burner does not ignite.
No fuel:
Turn on fuel.
Adjust regulator.
No spark:
Listen for audible spark, if not present try manual ignition
switch.
If spark is present, check the pressure switch and pressure
switch wiring.
If no spark is present check if electrode is gapped.
Check the battery. Replace if necessary.
Replace the high voltage ignition module.
Burner does not remain ignited.
If ignition occurs and unit continues to fire, but will not stabilize
(sustained combustion) note the position of the air shutters and
adjust for sustained ignition. Reset the air shutters when the
unit warms up.
Burner does not remain ignit-
ed when shut off valve button is
released
Replace thermocouple.
Replace shut off valve.
Output power or voltage low (TEG
in Set Up position).
Incorrect fuel adjustment, see section 2.10.
Incorrect air adjustment, see section 2.9.
Dirty fuel filter, orifice, or intake flame arrestors.
Protective limiter faulty.
Output power or voltage high.
Incorrect fuel adjustment, see section 2.10.
Output power or voltage low (TEG
in Operate position).
If any problems are encountered with the power conditioner, the
generator or electronics assembly should be removed to a safe
area.
37