background image

Page 16

Page 17

Lift Up Pressure & Temperature Relief Valve

This safety device is also pre-set at the factory and relieves before the temperature 

reaches 100°C. It is also a Pressure Relief Valve, and is pre-set to 6 bar.

Immersion Heaters

The immersion heaters fitted to our units are 3kW 240V ~AC. Check that the mains 

supply conforms to this, and all external wiring conforms to the most recent 

revision of the IEE wiring regulations. An Incoloy element is used on this product for 

standard domestic use and water conditions, use our Titanium elements in all other 

circumstances, part number SH002.

The immersion heater is fitted into the hot water cylinder using an O-ring. After the 

unit is filled with water check for leaks to determine if the O-ring has sealed and 

tighten carefully using the appropriate tool. To prevent damage to the O ring do not 

use excessive force to tighten the immersion heater.

The immersion heater is supplied with a thermostat which has been tested 

for operation in the cylinder and complies with the European directives for 

Electromagnetic compatibility and radio interference. It is Rated at 16 Amp 250V ~AC. 

Immersion Heater Wiring

E

L

N

Heating/primary Systems

The boiler and primary/heating systems should 

be sized and installed in accordance with BS 

EN 12828:2003, BS EN 12831:2003 & BS EN 

14336:2004.

Safety

StainlessLite Plus is fitted with a Combined Lift 

Up Temperature/Pressure Relief Valve to cope 

with any increase in system temperature and 

pressure above the design limitations, when 

used with boilers up to 45kW output, which is the 

maximum allowed by section G3 of the Building 

Regulations. The primary water temperatures 

should be controlled as outlined below.

Primary Circuit

It is essential that the circuit between the 

boiler and the StainlessLite Plus is pumped.  

The motorised zone valve supplied should 

be fitted adjacent to the unit and controlled 

by the cylinder thermostat supplied.  The 

thermostat and motorised valve must be wired 

so that they both switch off should an overheat 

situation develop.  When wiring the supplied 

components, it is important to follow the 

wiring diagram in the Wiring Section of these 

instructions.

Sealed Primary Circuit

Any boiler used must be fitted with an over 

temperature cut-out. Unvented primary circuits 

may be filled or replenished by means of a 

temporary connection between the circuit and 

a supply pipe provided a ‘Listed’ double check 

valve or some other no less effective backflow 

prevention device is permanently connected 

at the inlet to the circuit and the temporary 

connection is removed after use.

Alternatively, a CA device can be used, which 

will allow the system to be permanently 

connected to the cold mains supply. The 

primary system can then be topped up, when 

required, in the same way as an open vented 

system fitted with an F&E Cistern.

Gate Valve

All our cylinders are tested to BS EN 12897 at 15 

l/mim.

In extreme situations where excessive flow 

rates, above 25 l/min are present, then a gate 

valve on the return from the cylinder to the 

boiler, before it joins the central heating return, 

may be required to reduce excessive flow rates 

and therefore any potential noise problems.

Schematic Open Vented Primary System

Boiler

Pump

150mm max.

Warming/Overflow

Pipe

F & E Cistern

Minimum

distance as

required by

boiler

manufacturers

instructions

Motorised Valve

(Not supplied)

Motorised Valve
(Energy cut-out)

Gate Valve

(Not supplied)

Schematic Sealed Primary System

Boiler

Motorised Valve
(Energy cut-out)

Expansion

Vessel

Gauge

Safety Valve

Pump

Motorised Valve

(Not supplied)

Gate Valve

(Not supplied)

INSTALLATION

INSTALLATION

INSTALLATION

INSTALLATION

The immersion thermostat has two terminals 

A and B. The Live (brown) wire should be 

connected to terminal A and the Neutral (blue) 

wire should be connected to terminal B. It has 

been our experience that Crimp terminals make 

better connections. The immersion heater must 

be fully earthed (earth post) and connected via 

a double pole isolator switch having a contact 

separation at least 3mm, see diagram opposite.

Danger of electrocution: before making any 

adjustments to the thermostat isolate the 

immersion heater from the mains electricity 

supply at the fuse spur unit. 

The immersion heater thermostats incorporate 

a manual reset safety/overheat cut out 

thermostat. Should this operate, investigate 

the cause before pressing the red reset button 

labelled safety. If there is no apparent fault 

adjust the control setting down slightly to 

prevent nuisance tripping.

If another heat source is used to heat the 

cylinder and this is allowed to raise the water 

temperature excessively then the overheat 

thermostat will trip. This is likely on solar 

thermal products when the solar thermostats 

are set at high temperatures.

The Direct cylinder is intended to be heated 

from an off peak supply using the lowest 

immersion heater(s) and boosted via the upper 

immersion heater from an on peak supply. 

Suitable controllers are available to control this 

operation effectively.

Solar Thermistors / sensors

Care must be taken to ensure that the solar probes 

are fully inserted into the pockets provided.

Important

Failure to follow the drain down procedure will 

invalidate the warranty. (see page 22)

NEVER

 

drain the cylinder of hot water and 

then close all cylinder inlets and 

outlets. 

REASON

  as the air remaining in the cylinder 

cools the pressure inside the 

cylinder will fall below atmospheric 

and cause damage to the cylinder.

NEVER

 

close the cold main and drain the 

cylinder via any tap connected to it.

REASON

  as the water drains, the pressure 

inside the cylinder may decrease 

below atmospheric and this may 

cause damage to the cylinder.

In line with good plumbing practice, use of 

excessive flux should be avoided.

I.V.

Combination Valve

I.V.

If two StainlessLite Plus cylinders are coupled together the secondary inlet and outlet 

pipes must be balanced. The units must be fitted on the same level.

Note: No valves must be fitted between the expansion vessel and the storage cylinder(s).

Thermostat Type TSR fitted in the 

Direct cylinders; is supplied set at 

62°C ± 3°C. Position 4 is 55°C ± 3°C 

and position 5 is 68°C ± 3°C. 

Thermostat Type TSE fitted in the 

indirect cylinders - is supplied set 

in position 5 at 60°C ± 4°C.

When ordering a replacement 

part the TSR thermostat type will 

be supplied with the immersion 

heater.

Summary of Contents for StainlessLite Plus Direct D120

Page 1: ...WWW GLEDHILL NET ONE NAME EVERY SOLUTION STAINLESSLITE PLUS UNVENTED MAINS PRESSURE HOT WATER STORAGE INSTRUCTION MANUAL DESIGN INSTALLATION SERVICING ...

Page 2: ...faninstallationorsystem containing one of our products unless specifically requested to do so in writing All goods are sold subject to our Conditions of Sale which are set out at the rear of this specification In the interest of continuously improving the StainlessLite Plus range Gledhill Building Products Limited reserve the right to modify the product without notice and in these circumstances th...

Page 3: ... designed for use with a gas or oil boiler and is suitable for both open vented and sealed pumped primary systems When used with a sealed heating system the boiler must incorporate its own energy cut out overheat thermostat StainlessLite Plus Indirect models are listed in Table 2 on Page 8 9 StainlessLite Plus DIRECT StainlessLite Plus INDIRECT StainlessLite Plus DIRECT SOLAR StainlessLite Plus IN...

Page 4: ...89 37 2698 62 15 91 18 106 3 12 976 475 750 n a n a 210 227 n a n a n a n a n a n a n a n a n a 90 n a D120 SL PLUDR120SL L C 47 1 13 37 2765 62 15 122 23 143 3 12 1248 475 1022 n a 680 210 227 53 2 n a n a n a n a n a n a n a n a 119 n a D150 SL PLUDR150SL M C 56 1 37 36 1425 62 15 152 27 176 3 18 1519 475 1293 n a 832 210 227 66 6 n a n a n a n a n a n a n a n a 150 n a D180 SL PLUDR180SL L C 67...

Page 5: ... n a n a n a n a n a 30 5 1 27 0 31 n a n a 41 n a Indirect Slimline IND60 SL PLUIN060SL A 27 0 66 62 16 75 3 12 704 475 478 n a 393 325 n a 24 3 253 n a 195 305 n a n a n a n a n a n a 15 0 49 0 165 n a n a 13 n a IND90 SL PLUIN090SL B 37 0 89 91 20 108 3 12 976 475 750 n a 453 365 n a 48 1 343 n a 195 345 n a n a n a n a n a n a 16 5 0 59 0 165 n a n a 17 n a IND120 SL PLUIN120SL B 47 1 13 122 2...

Page 6: ...Hot water draw off 22mm compression 2 Lift up temperature pressure relief valve 89 96 6 bar 3 Hot water secondary return 22mm not fitted to smaller sizes see table 1 4 Immersion heater 1 BSP 3kW normally on peak 5 22mm cold supply 6 Immersion heater 1 BSP 3kW normally off peak 7 Dual control Overheat stat pocket solar 8 Solar coil return to panel collector 22mm compression 9 Solar coil flow from p...

Page 7: ...ixing valve canbeusedaslongasboththehotandcoldsuppliesaremainsfed However allmains pressure systems are subject to dynamic changes particularly when other hot and cold taps showersareopenedandclosed whichwillcausechangesinthewatertemperature at mixed water outlets such as showers For this reason and because these are now no moreexpensivethanamanualshowerwestronglyrecommendtheuseofthermostatic show...

Page 8: ...orage systems are installed where discharges form safety devices may not be apparent i e in dwellings occupied by blind infirm or disabled people consideration should be given to the installation of an electronically operated device to warn when discharge takes place Safety The safety devices supplied or fitted on an StainlessLite Plus are selected for their suitability for the temperatures and pr...

Page 9: ... the central heating return may be required to reduce excessive flow rates and therefore any potential noise problems Schematic Open Vented Primary System Boiler Pump 150mm max Warming Overflow Pipe F E Cistern Minimum distance as required by boiler manufacturers instructions Motorised Valve Not supplied Motorised Valve Energy cut out Gate Valve Not supplied Schematic Sealed Primary System Boiler ...

Page 10: ...lding regulations part G3 3 63 This product can be supplied from Gledhill part number XC007 which has a inlet temperature limit of 100 C Suitable plumbing configurations for installing this valve are shown on page 19 of this manual NB Any fitted Overheat thermostats may require resetting in the winter months to enable backup heat sources to heat the cylinder Schematic Solar Indirect System Solar P...

Page 11: ...lator 230 VAC 5 Amps HTG VALVE HW VALVE Typical schematic wiring diagram for an unvented installation The electrical installation must comply with IEE requirements For electrical installation refer to BS7671 Note Do not attempt the electrical work unless you are competent to carry out to the above standard Blue Bl Brown Br Green Grey Green Yellow G Gr G Y WIRE COLOUR LEGEND Black Orange Yellow Whi...

Page 12: ...ements When initially opening the taps a small surge in flow may be experienced which disappears as the pressure in the system stabilises This is quite normal with these types of systems and does not indicate a fault In some areas the water will initially appear cloudy but will quickly clear when left to stand This is nothing to be concerned about and is due to aeration of the water WARNING Ifwate...

Page 13: ...ning for drain down procedure If there is an overheat fault and very hot water is being discharged turn off the heat source but not the water supply When the supply is cool check thermostats and energy cut outs in the boiler and immersion heaters and replace the faulty component with one supplied by Gledhill and check that it works correctly before returning the system to full operation The Regist...

Page 14: ...d seat clean undamaged Is heater operating at less than 60ºC Re set temperature NO YES YES NO NO YES YES Is ERV TPRV discharging YES Recommission expansion vessel pressure NO NO FAULT No Hot Water Direct FAULT No Hot Water Indirect Switch on Re set Replace element START Is power on to elements Is control temperature set at 60ºC 65ºC Has high limit tripped Check wiring links continuity and Re set E...

Page 15: ...ed Regulators Aerator forscrewingontoTaps Mixerswithinternal orexternalthreadsontheirnoses AntiVandal models also available 2 MR05 T Range Internal Regulators Push fit into Tap or Mixer seats Produced in three sizes 12 5mm BS1010 12mm 10mm Flangeless models also available for Taps with Low Lift washers 3 MXF Standard Range Screw on tail models for Taps Mixers Fix onto the tails before fitting the ...

Page 16: ...nual handling operation Residual risk Following the guidelines given above will reduce any risk to injury All persons carrying out this operation must be fully trained and copies of the specific risk assessment made available for inspection and use in their training process Further guidance on Manual Handling can be obtained from the Health and Safety Executive Manual Handling Operations Regulatio...

Page 17: ...e which are contained on the Invoice Forms and all Sales are now subject to these Conditions of Sale and Warranty terms only 2 PRICE Once an order or call off has been accepted the price will be held for three months but if delivery is extended beyond that period at the customer s request then we reserve the right to amend the price when necessary The company reviews its pricing annually to adjust...

Page 18: ...o Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Comments Signature SERVICE 09 Date Engineer name Company name Telephone No Comments Signature SERVICE 02 Date Engineer name Company name Telephone No Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Comments Signature SERVICE 06 Date Engineer name Company name Telephone No Comments Signature SERV...

Page 19: ...3 474412 OR WWW GLEDHILL SPARES NET Due to a programme of continuous improvement Gledhill Building Products reserve the right to modify products without prior notice It is advisable to check the product technical detail by using the latest design and installation manuals available from our technical support team or on our website It is an offence to copy or adapt this document without consent of t...

Reviews: