background image

Page 14

Page 15

15 mm

discharge

pipe

Expansion

relief valve

Typical Discharge Pipe Arrangement

Dotted line showing

alternative route with

single tundish being used

600 mm max.

P & T 

Relief 

Valve

300 mm

min.

22 mm metal pipe with continuous

fall up to 9m equivalent length (D2).

NOTES:

 

The discharge will consist of scalding

water and steam. Asphalt, roofing felt

and non-metallic rainwater goods may

be damaged by such discharges.
It is not acceptable to discharge straight

into a soil pipe.

Discharge below

fixed grating

Fixed Grating

Trapped gully

Pressure & Temperature/expansion Relief 

Valve Pipework

The relief valve should be installed to discharge  

in accordance with G3 of the Approved 

Document of the Building Regulations and 

should be piped to where it is visible, but will 

not cause danger to persons or damage to 

materials.

The following information is taken from 

Approved Document G3 of the Building 

Regulations and is provided to assist with 

the design and installation of the discharge 

pipework. However, the information is not 

exhaustive and reference should always be 

made to Approved Document G3 of the Building 

Regulations. The final decision regarding any 

arrangements rests with Building Control and 

it is recommended that their advice is sought 

if you have any concerns regarding this aspect 

of the installation.

The two safety valves will only discharge 

water under fault conditions.  When operating 

normally water will not be discharged.  

The tundish should be vertical, located in the 

same space as the unvented hot water storage 

system and be fitted as close as possible and 

within 600mm of the safety device e.g. the 

temperature relief valve.

The discharge pipe (D2) from the tundish should 

terminate in a safe place where there is no risk 

to persons in the vicinity of the discharge, be 

of metal and:

a) Be at least one pipe size larger than the 

nominal outlet size of the safety device unless 

its total equivalent hydraulic resistance 

exceeds that of a straight pipe 9m long 

i.e. discharge pipes between 9m and 18m 

equivalent resistance length should be at 

least two sizes larger than the nominal outlet 

size of the safety device, between 18 and 

27m at least 3 sizes larger, and so on.  Bends 

must be taken into account in calculating 

the flow resistance.  Refer to the table and 

the worked example.

  An alternative approach for sizing discharge 

pipes would be to follow BS EN 806-2:2005 

Specification for design installation, testing 

and maintenance of services supplying water 

for domestic use within buildings and their 

curtilages.

b) Have a vertical section of pipe at least 

300mm long, below the tundish before any 

elbows or bends in the pipe work.

c)  Be installed with a continuous fall.

d)  It is preferable for the discharge to be visible at both the tundish and the final point 

of discharge but where this is not possible or practically difficult there should be 

clear visibility at one or other of these locations.  Examples of acceptable discharge 

arrangements are:

1.  Ideally below the fixed grating and above the water seal in a trapped gulley.

2.  Downward discharges at a low level; i.e. up to 100mm above external surfaces 

such as car parks, hard standings, grassed areas etc are acceptable providing that 

where children play or otherwise come into contact with discharges, a wire cage 

or similar guard is positioned to prevent contact whilst maintaining visibility.

3.   Discharges at a high level; e.g. into metal hopper and metal down pipe with the 

end of the discharge pipe clearly visible (tundish visible or not) or onto a roof 

capable of withstanding high temperature discharges of water and 3m from 

any plastic guttering systems that would collect such discharges.

4.   Where a single common discharge pipe serves more than one system, it should 

be at least one pipe size larger than the largest individual discharge pipe (D2) 

to be connected.

5.  If unvented hot water storage systems are installed where discharges form 

safety devices may not be apparent i.e. in dwellings occupied by blind, infirm 

or disabled people, consideration should be given to the installation of an 

electronically operated device to warn when discharge takes place.

Safety

The safety devices supplied or fitted on an StainlessLite Plus are selected for their 

suitability for the temperatures and pressures involved.  They must not be changed, 

removed or by-passed and it is essential that only genuine replacement parts supplied 

or approved by Gledhill Building Products Limited are used. All parts are available to 

approved installers from Gledhill Building Products Limited, Sycamore Estate, Squires 

Gate, Blackpool (Telephone 01253 474402).

Tundish

Hot Outlet

To Drain

PRV

NRV

Stop

Tap

Kitchen

Cold

Tap

Combination

Valve

Balanced

Cold

Outlets

P&T

Relief Valve

Immersion Heater

Expansion Vessel(s)

Boiler

Return

Boiler

Flow

2 Port Valve

Secondary

Return Circuit

Schematic Diagram

Non Return

Valve

Pump

ERV

Worked Example

The example below is for G1/2 temperature relief valve with a discharge pipe (D2) 

having 4 elbows and length of 7m from the tundish to the point of discharge.

From the table below:

Maximum resistance allowed for a straight length of 22mm copper discharge 

pipe (D2) from a G1/2 temperature relief valve is: 9m subtract the resistance for 

4 x 22mm elbows at 0.8m each = 3.2m.

Therefore the maximum permitted length equates to: 5.8m.

5.8m is less than the actual length of 7m therefore calculate the next largest size.

Maximum resistance allowed for a straight length of 28mm pipe (D2) from a G1/2 

temperature relief valve equates to: 14m.

As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.

Sizing of copper discharge pipe ‘D2’ for a temperature relief valve

with a G1/2 outlet size (as supplied)

Size of discharge 

pipework

Maximum length of 

straight pipe

(no bends or elbows)

Deduct the figure 

below from the 

maximum length for 

each bend or elbow in 

the discharge pipe

22mm

Up to 9m

0.8m

28mm

Up to 18m

1m

35mm

Up to 27m

1.4m

INSTALLATION

INSTALLATION

INSTALLATION

INSTALLATION

Line Strainer

This is integral within the combination inlet 

group to reduce the likelihood of contaminants 

fouling the valve seat.  Following installation this 

line strainer must be cleaned and replaced.  This 

needs to be carried out on a regular basis. as part 

of the annual maintenance/service check.

Tundish

This is to allow the discharge from any Relief 

Valve to be seen.  It must be fitted away from 

any electrical devices.  See page 14 for discharge 

pipework details.

Expansion Vessels Installation

To prevent water stagnation and particulate 

accumulation affecting water quality, it is 

recommended that the expansion vessel be 

installed in the vertical orientation so that the 

fitting accommodating thermal expansion or a 

pressure surge is:- 

1.  bottom fed and upright; and 

2.   that the connecting pipework to the fitting:- 

        - rises continuously; and 

        - is kept to a minimum;

2 expansion cylinders on 400 litre Models

All 400 litre models are supplied with two 24 

litre expansion cylinders. These can be coupled 

together and fitted to the expansion cylinder 

tapping on the combination inlet valve, or by 

some other means on the cold/hot water inlet 

pipework. There must be no valve on the pipe 

work between the expansion cylinders and the 

unvented cylinder which could prevent the 

expansion of the water contained in the unvented 

cylinder reaching the expansion cylinders.

Combination Inlet Group

Combines elements 1, 2 and 3 below.

1.  

Pressure Reducing Valve

 - The cold water 

supply to any mixer taps/showers must 

be taken from the cold water tapping of 

this valve to ensure balanced hot and cold 

pressures.  This valve is factory set to ensure 

the correct operating pressure for the 

StainlessLite Plus.

2. 

Non Return Valve 

- This is integral with the 

pressure reducing valve to prevent backflow of 

hot water towards cold water draw off points.

3.  

Cold Water Expansion Relief Valve

 - This safety 

device is preset at the factory and will relieve 

excess cold water pressure resulting from a 

fault condition.

Summary of Contents for StainlessLite Plus Direct D120

Page 1: ...WWW GLEDHILL NET ONE NAME EVERY SOLUTION STAINLESSLITE PLUS UNVENTED MAINS PRESSURE HOT WATER STORAGE INSTRUCTION MANUAL DESIGN INSTALLATION SERVICING ...

Page 2: ...faninstallationorsystem containing one of our products unless specifically requested to do so in writing All goods are sold subject to our Conditions of Sale which are set out at the rear of this specification In the interest of continuously improving the StainlessLite Plus range Gledhill Building Products Limited reserve the right to modify the product without notice and in these circumstances th...

Page 3: ... designed for use with a gas or oil boiler and is suitable for both open vented and sealed pumped primary systems When used with a sealed heating system the boiler must incorporate its own energy cut out overheat thermostat StainlessLite Plus Indirect models are listed in Table 2 on Page 8 9 StainlessLite Plus DIRECT StainlessLite Plus INDIRECT StainlessLite Plus DIRECT SOLAR StainlessLite Plus IN...

Page 4: ...89 37 2698 62 15 91 18 106 3 12 976 475 750 n a n a 210 227 n a n a n a n a n a n a n a n a n a 90 n a D120 SL PLUDR120SL L C 47 1 13 37 2765 62 15 122 23 143 3 12 1248 475 1022 n a 680 210 227 53 2 n a n a n a n a n a n a n a n a 119 n a D150 SL PLUDR150SL M C 56 1 37 36 1425 62 15 152 27 176 3 18 1519 475 1293 n a 832 210 227 66 6 n a n a n a n a n a n a n a n a 150 n a D180 SL PLUDR180SL L C 67...

Page 5: ... n a n a n a n a n a 30 5 1 27 0 31 n a n a 41 n a Indirect Slimline IND60 SL PLUIN060SL A 27 0 66 62 16 75 3 12 704 475 478 n a 393 325 n a 24 3 253 n a 195 305 n a n a n a n a n a n a 15 0 49 0 165 n a n a 13 n a IND90 SL PLUIN090SL B 37 0 89 91 20 108 3 12 976 475 750 n a 453 365 n a 48 1 343 n a 195 345 n a n a n a n a n a n a 16 5 0 59 0 165 n a n a 17 n a IND120 SL PLUIN120SL B 47 1 13 122 2...

Page 6: ...Hot water draw off 22mm compression 2 Lift up temperature pressure relief valve 89 96 6 bar 3 Hot water secondary return 22mm not fitted to smaller sizes see table 1 4 Immersion heater 1 BSP 3kW normally on peak 5 22mm cold supply 6 Immersion heater 1 BSP 3kW normally off peak 7 Dual control Overheat stat pocket solar 8 Solar coil return to panel collector 22mm compression 9 Solar coil flow from p...

Page 7: ...ixing valve canbeusedaslongasboththehotandcoldsuppliesaremainsfed However allmains pressure systems are subject to dynamic changes particularly when other hot and cold taps showersareopenedandclosed whichwillcausechangesinthewatertemperature at mixed water outlets such as showers For this reason and because these are now no moreexpensivethanamanualshowerwestronglyrecommendtheuseofthermostatic show...

Page 8: ...orage systems are installed where discharges form safety devices may not be apparent i e in dwellings occupied by blind infirm or disabled people consideration should be given to the installation of an electronically operated device to warn when discharge takes place Safety The safety devices supplied or fitted on an StainlessLite Plus are selected for their suitability for the temperatures and pr...

Page 9: ... the central heating return may be required to reduce excessive flow rates and therefore any potential noise problems Schematic Open Vented Primary System Boiler Pump 150mm max Warming Overflow Pipe F E Cistern Minimum distance as required by boiler manufacturers instructions Motorised Valve Not supplied Motorised Valve Energy cut out Gate Valve Not supplied Schematic Sealed Primary System Boiler ...

Page 10: ...lding regulations part G3 3 63 This product can be supplied from Gledhill part number XC007 which has a inlet temperature limit of 100 C Suitable plumbing configurations for installing this valve are shown on page 19 of this manual NB Any fitted Overheat thermostats may require resetting in the winter months to enable backup heat sources to heat the cylinder Schematic Solar Indirect System Solar P...

Page 11: ...lator 230 VAC 5 Amps HTG VALVE HW VALVE Typical schematic wiring diagram for an unvented installation The electrical installation must comply with IEE requirements For electrical installation refer to BS7671 Note Do not attempt the electrical work unless you are competent to carry out to the above standard Blue Bl Brown Br Green Grey Green Yellow G Gr G Y WIRE COLOUR LEGEND Black Orange Yellow Whi...

Page 12: ...ements When initially opening the taps a small surge in flow may be experienced which disappears as the pressure in the system stabilises This is quite normal with these types of systems and does not indicate a fault In some areas the water will initially appear cloudy but will quickly clear when left to stand This is nothing to be concerned about and is due to aeration of the water WARNING Ifwate...

Page 13: ...ning for drain down procedure If there is an overheat fault and very hot water is being discharged turn off the heat source but not the water supply When the supply is cool check thermostats and energy cut outs in the boiler and immersion heaters and replace the faulty component with one supplied by Gledhill and check that it works correctly before returning the system to full operation The Regist...

Page 14: ...d seat clean undamaged Is heater operating at less than 60ºC Re set temperature NO YES YES NO NO YES YES Is ERV TPRV discharging YES Recommission expansion vessel pressure NO NO FAULT No Hot Water Direct FAULT No Hot Water Indirect Switch on Re set Replace element START Is power on to elements Is control temperature set at 60ºC 65ºC Has high limit tripped Check wiring links continuity and Re set E...

Page 15: ...ed Regulators Aerator forscrewingontoTaps Mixerswithinternal orexternalthreadsontheirnoses AntiVandal models also available 2 MR05 T Range Internal Regulators Push fit into Tap or Mixer seats Produced in three sizes 12 5mm BS1010 12mm 10mm Flangeless models also available for Taps with Low Lift washers 3 MXF Standard Range Screw on tail models for Taps Mixers Fix onto the tails before fitting the ...

Page 16: ...nual handling operation Residual risk Following the guidelines given above will reduce any risk to injury All persons carrying out this operation must be fully trained and copies of the specific risk assessment made available for inspection and use in their training process Further guidance on Manual Handling can be obtained from the Health and Safety Executive Manual Handling Operations Regulatio...

Page 17: ...e which are contained on the Invoice Forms and all Sales are now subject to these Conditions of Sale and Warranty terms only 2 PRICE Once an order or call off has been accepted the price will be held for three months but if delivery is extended beyond that period at the customer s request then we reserve the right to amend the price when necessary The company reviews its pricing annually to adjust...

Page 18: ...o Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Comments Signature SERVICE 09 Date Engineer name Company name Telephone No Comments Signature SERVICE 02 Date Engineer name Company name Telephone No Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Comments Signature SERVICE 06 Date Engineer name Company name Telephone No Comments Signature SERV...

Page 19: ...3 474412 OR WWW GLEDHILL SPARES NET Due to a programme of continuous improvement Gledhill Building Products reserve the right to modify products without prior notice It is advisable to check the product technical detail by using the latest design and installation manuals available from our technical support team or on our website It is an offence to copy or adapt this document without consent of t...

Reviews: