background image

o

Switch on mains voltage.

i

The 1-10 V ballasts can be switched by briefly pressing the 

Prog

 button.

Status-LED (3) lights up: switched on
Status-LED (3) off: switched off

o

Perform commissioning.

i

In installation positions that are not easily accessible, turn the operating mode switch to
position 

PC

 after commissioning and performing a function test. Subsequent changes to

the device settings can thus be carried out with the aid of the eNet-Server without involving
excessive installation work.

o

Mount the cover.

5.2 Commissioning

DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
During commissioning, cover the parts carrying voltage on radio transmitters
and actuators and in their surrounding area.

i

The actuator can also be commissioned with eNet server as an alternative to the
commissioning described here.

Connecting to radio transmitters 

Load is switched off.

o

Press the 

Prog

 button for longer than 4 seconds.

The status LED (4) flashes after 3 seconds. The actuator is in programming mode for
approx. 1 minute.

o

Switch radio transmitter to programming mode (see radio transmitter instructions).

o

Trigger telegram on the radio transmitter.
The status LED lights up for 5 seconds.
The actuator is connected to the radio transmitter. The actuator and radio transmitter exit
the programming mode automatically.

i

If the status LED of the control unit flashes 3 times at 1-second intervals for
approx. 5 seconds, then the programming operation was not successful. All the memory
locations in the actuator or radio transmitter are occupied. 

i

All On and All Off buttons of a radio transmitter are connected to the actuator automatically
as soon as the first connection to the radio transmitter takes place. Scene buttons must be
connected separately.

 Disconnecting connection to a radio transmitter

o

Carry out the same steps as when connecting (see Connecting to radio transmitter). 
The status LED (3) flashes quickly for 5 seconds. The actuator is disconnected from the
radio transmitter. The actuator and radio transmitter exit the programming mode
automatically.

i

If there several connections or scene buttons for a radio transmitter, all connections must
be disconnected individually.

i

All On and All Off buttons of a radio transmitter are disconnected automatically as soon as
the last connection to the radio transmitter is disconnected. Manual disconnection is not
possible. 

Resetting actuator to default setting

All connections to radio transmitters are disconnected and parameters are reset to default
setting.

i

The connections in the radio transmitters are preserved and must be deleted separately.

Load is switched off.

32581002

10499448

13.03.2014

4/11

eNet

Radio control unit 1-10V, 1-gang Mini

Summary of Contents for eNet

Page 1: ...the end customer 2 Device components Figure 1 Device components 1 Operating mode switch 2 Button Prog 3 Status LED 4 Measuring points for voltage measurement terminals rear mounted 3 Function System...

Page 2: ...d signalling could vary from what is described here i The parameter list is in the Internet in the documentation for this device Supplementary functions with eNet server Update of the device software...

Page 3: ...ous voltages to the device or load couple the miniature circuit breakers or label them with a warning to ensure disconnection is guaranteed o Insert the actuator in the appliance box in such a way tha...

Page 4: ...r The actuator and radio transmitter exit the programming mode automatically i If the status LED of the control unit flashes 3 times at 1 second intervals for approx 5 seconds then the programming ope...

Page 5: ...r longer than 4 seconds The light switches off briefly and then switches on again to the new switch on brightness Switch on brightness is saved i Alternatively the switch on brightness can be saved wi...

Page 6: ...tory setting Operating mode Normal operation Continuous on Continuous off Basic setting Normal Operation Normal operation The output can be operated with radio transmitters and the Prog button Continu...

Page 7: ...as not yet been switched off due to the delay when a switch on command comes then the load will remain on Note The set time apply to operation using radio transmitters The device is switched immediate...

Page 8: ...he Prog button is pressed Behaviour after the end of the disabling function On Off no change Last value Basic setting No change Behaviour of the output when a block is removed Behaviour on voltage ret...

Page 9: ...is the highest priority and 4 the lowest 0 means no priority Priority restraint 0 4 Basic setting 2 Specifies the priority for recalling and removing a scene of type Forced position for the channel Pr...

Page 10: ...a level higher than the maximum brightness then the system will dim to maximum brightness Hotel function On Off Basic setting Off If the hotel function is activated the system will dim to 20 brightnes...

Page 11: ...Eliminate short circuit Lamps switch to maximum brightness No dimming is possible Cause 1 10 V control cables are interrupted or not connected Connect the control cables correctly 6 4 Accessories Ins...