6.2. Object table
Communication objects: 114
Addresses (max.):
32767
Assignments (max.):
32767
Dynamic
table management:
No
The alarm control unit Connect offers the following group objects for integrating group addresses:
Object
Name
Function
Type
DP type
Flags
1
Alarm control unit
Ready
1 bit
1.011 status
C, R, T
Object which returns the state of the device. If the value of the object is "1", the device is ready for
operation. "0" means that the device is not yet ready for operation.
Object
Name
Function
Type
DP type
Flags
2
Alarm control unit
Status
1 byte
5.010 meter
pulses (0..255)
C, R, T
Object for transmitting the current device state.
00h
Ready
The alarm control unit Connect is ready for operation.
01h
Booting
The alarm control unit Connect is booting.
02h
Shutting down
The alarm control unit Connect will reboot.
03h
Configuring
The alarm control unit Connect is currently being con-
figured.
04h...FFh Reserved
Object
Name
Function
Type
DP type
Flags
6
Alarm control unit
Date
3 bytes
11.001 date
C, W
The alarm control unit Connect is time client. Object for receiving the current date.
Object
Name
Function
Type
DP type
Flags
7
Alarm control unit
Time
3 bytes
10.001 time of
day
C, W
The alarm control unit Connect is time client. Object for receiving the current time.
Object
Name
Function
Type
DP type
Flags
8
Alarm control unit
Runtime (s)
4 bytes
13.100 time dif-
ference (s)
C, R
Object for transmitting the operating time in seconds. Time since last restart.
Object
Name
Function
Type
DP type
Flags
50
Alarm control unit
Programming
mode
1 bit
1.001 switching C, W
Show KNX alarm communication objects: Active. Object for receiving the programming mode. "1"
means that programming mode is activated, and "0" means that programming mode is deactivated.