Installation and electrical connection
Order No. 5201 00
Page 8
Use power lines with a cable cross-section of 1.5 to 2.5
mm².
AMT
Connection: TAE box
TEL
Connection: telephone
LAN
Connection: Ethernet cable
Connection example for inputs
The following cable type can be connected to the inputs:
IY(ST)Y with Ø 0.6 to 0.8 mm, max. length 100 m.
INPUTS
Input plug terminals
12V
DC 12 V, max. 1 A
GND
Ground is wired as a signal
IN1, IN2
Contact (NC/NO)
A
Example: Fault relay heating system
Connection example for outputs
OUTPUTS
Output plug terminals
12V
DC 12 V, max. 200 mA
GND
Ground
OUT1, OUT2
Open-Drain
Max. switching current: DC 12 V/200 mA
1. Connect the Ethernet cable to the LAN port.
2. Connect the battery pack and switch on the mains voltage. Wait for the initialisation phase.
3. Configure the project in the GPA and transfer it to the alarm centre memory (also see the enclosed
Quick Start Guide).
4. Close the hinged cover on the battery compartment and tighten the two screws.
Leave the housing cover off and stay in configuration mode.