38
Model: GVH-C & GVH-F
Operation & Filter Maintenance
③
SNOOZE Button
In the event that
[TIMEOUT]
has occurred during a period of high
customer demand or while cooking is in progress, a snooze feature
may be used. Pressing the
[SNOOZE]
Button will temporarily reset
the timer to
[WARNING]
mode for a period of
two (2) hours
, allowing
continued operation.
NOTE: Hood must be restarted as described in
Section 4.01
.
Two (2) snooze periods are allowed. During a second snooze period, the
[CHANGE SOON]
light flashes,
indicating the timer is in the final snooze period. After second snooze period expires, appliance power is
locked-out until the E.A.C. cell is cleaned
(or exchanged)
.
4.04
E.A.C. Filter Cell Cleaning Timer Operation
The unit is equipped with an
E.A.C. Filter Cell Cleaning Timer
. This feature was designed to help users maintain a
proper cleaning routine for the cell. Timely cleaning is essential to ensuring the hood continues to effectively clean
the recirculated air.
After a preset amount of time, a signal is issued indicating it is time for the collector cell to be cleaned
(or
exchanged with a clean one)
. If cleaning
(or exchange)
is not completed within a preset time, the timer expires and
power to the appliances is shutdown and will remain
OFF
until cleaning
(or exchange)
is complete. When the
necessary filter maintenance is performed, the timer automatically resets and normal operation is restored and a
fresh timer countdown begins.
Should a shutdown occur during a peak demand period or while a cooking is in progress, a
SNOOZE
feature is
provided to temporarily continue operation for a short time.
Timer indicator lights and
[SNOOZE]
Button are located on the control panel.
①
CHANGE SOON
The amber indicator turns
ON
when timer enters
[WARNING]
mode. If the collector cell is cleaned
(or
exchanged)
within the next
24 hours
, timer automatically resets and begins a new countdown. Normal
operations continue without interruption.
②
CHANGE NOW
The red indicator turns
ON
when timer enters
[TIMEOUT]
mode, signaling that allowed time between
cleanings has expired. An audible alarm sounds and appliance power
is turned
OFF
. It will remain disabled until cell cleaning
(or exchange)
is completed. The Hood
[POWER]
and
[APPLIANCE POWERED]
lights
will turn
OFF
.
Placing the
Power Switch
in the
[OFF]
position silences the alarm, but
the hood will restart until the Timer is reset by cleaning
(or
exchanging)
the cell.
Timer Operation:
1
2
3
Summary of Contents for GVH-C
Page 2: ......
Page 4: ......
Page 13: ...3 Model GVH C GVH F Introduction 1 04 1 Overall Dimensions GVH F Floor Stand Version ...
Page 18: ...8 Model GVH C GVH F Installation 2 03 2 GVH Floor Stand Hood GVH F ...
Page 34: ...Model GVH C GVH F Overview 24 1 5 2 4 3 8 9 3 01 Control Panel 6 7 ...
Page 49: ...39 Model GVH C GVH F Operation Filter Maintenance ...
Page 56: ...46 Model GVH C GVH F Troubleshooting ...
Page 64: ...54 Parts List Model GVH C GVH F 7 05 Under Hood Components 2 1 4 3 ...
Page 66: ...56 Model GVH C GVH F Parts List ...
Page 67: ......