Connection logical input
The logic input is isolated from the instrument through an optocoupler.
The connection cable of the logic input must not be channeled with power or power cables
Use a connection cable as short as possible (no longer than 5 meters). If a longer length is
required, use a relay relay.
In the case of DC power supply (e
.
g
.
24 V dc) and a long or disturbed input connection cable,
we recommend connecting pin 13 (input) and 14 (+ power supply) instead of 12 and 13
Relay output connection
The three outputs are relayed with three commons. The capacity of each contact is 24 V DC / VAC 0.5 A.
Serial RS485 connection
The cable must not be channeled with other cables (e.g. outputs connected to remote control
switches or power supply cables), it must possibly follow its own path.
!
!
!