background image

 

 

Manuale 
Manual 
Handbuch 

Summary of Contents for WIN6

Page 1: ...Manuale Manual Handbuch...

Page 2: ...Manuale d istallazione e d uso Installation and user manual Installations und Bedienungsanleitung LIMITATORE di carico load LIMITER LASTBEGRENZER...

Page 3: ...t not detectable 11 Signal of underweight 11 Overload signal 11 LED indicators red 11 Other LED indicators green 11 Use of the keyboard 12 Data setting 12 Restore zero semi automatic zero 12 Self weig...

Page 4: ...Offset adjustment calibration 19 Limit values 19 Output configuration 20 Set point programming 20 Excitation delay 20 Programming polarity of intervention of the logic output 3 20 Serial protocol 21...

Page 5: ...f full scale C Internal resolution 24 bit Measuring range From 3 9 mV V to 3 9 mV V Output rate 10 Hz Digital filter 0 1 Hz 10 Hz selectable Weight decimals From 0 to 3 decimals Calibration Zero and f...

Page 6: ...by specialized operators All connections have to be executed with the instrument shut off Identification plate of the instrument It is important to communicate this data in case of request for informa...

Page 7: ...ding or through support terminal blocks or through the junction box supplied separately The cell cable must have a number of conductors not higher than those used 4 or 6 In the case of a multi conduct...

Page 8: ...lay In the case of DC power supply e g 24 V dc and a long or disturbed input connection cable we recommend connecting pin 13 input and 14 power supply instead of 12 and 13 Relay output connection The...

Page 9: ...nection diagram with a 9 pole PC connector is shown below Connection of analog output optional The instrument when it is in this hardware configuration provides an analogue output in current or in vol...

Page 10: ...is of the differential type i e the signal is the result of the difference between the voltages of the two wires that make up the bus The RS485 RS422 transmitters provide under load an output level o...

Page 11: ...e is indicated in the figure opposite but this applies to very long lines hundreds of meters In the case of shorter lines the resistances must be increased because the total impedance with the 120 Ohm...

Page 12: ...Pagina page Seite 10...

Page 13: ...mmuni cate these codes in case of request for assistance When a programming procedure is not in progress the display shows the measured weight expressed in kg Under certain conditions the following me...

Page 14: ...automatic zero This operation is performed to correct small shifts of the zero of the instrument The gross weight reset command is not executed under the following conditions Weight instable the weig...

Page 15: ...of zero its output is always de energized All relays de energize alarm condition when the following conditions occur cell cable breakages or weight outside the nominal range NO CON or exceeding the m...

Page 16: ...m a theoretical weight calibration After a change the set points are reset Password pro setting Divisions value The division value is expressed in kg selectable between 0 001 kg and 50 kg The ratio be...

Page 17: ...lized weight The displayed weight must be reset This operation can be repeated several times Full scale calibration Before carrying out the operation load the sample weight on the scale and wait for i...

Page 18: ...weight variations is obtained In the second one we get a slowing of the weight response on the display which allows to absorb oscillations or vibrations of the weighing system Weight stability The wei...

Page 19: ...zero scale Value Variation 0 Tracking function of zero excluded 1 Minimum zero tracking intervention 2 Medium zero tracking intervention standard 3 High zero tracking intervention 4 Maximum zero track...

Page 20: ...Analog output set up and test menu optional Pagina page Seite 18...

Page 21: ...e arrow keys to adjust the analogue output Press and hold the key for a quick change Limit values When the weight exceeds the programmed full scale the output assumes a value higher than the full scal...

Page 22: ...trument can only be used with a weight lower than a set threshold When the weight is not detectable or out of scale the relays are all de energized open contact Excitation delay Output excitation dela...

Page 23: ...ing of 8 ASCII characters with the weight value justified on the right In overweight conditions the field assumes the value In underweight conditions the field assumes the value _ _ _ _ _ _ _ _ Under...

Page 24: ...miautomatic zero To restore zero the weight must be calibrated The weight does not stabilize Wait for the weight to stabilize or adjust the weight filter parameter The autotara function does not work...

Page 25: ...Pagina page Seite 23...

Page 26: ...Pagina page Seite 24...

Page 27: ...materiale disponibile sul nostro sito www gricamgra com The latest version of this manual can be downloaded from our website www gicamloadcells com Die neueste Version dieses Handbuches finden Sie auf...

Page 28: ......

Reviews: