31
6. Variable - SP2
Description: Set point 2
Data type: Signed short
Range: spLL to sphL
Decimal dependence: dP
READ/WRITE: Read/Write
Address (in HEX): 2006
7. Variable - SP3
Description: Set point 3
Data type: Signed short
Range: spLL to sphL
Decimal dependence: dP
READ/WRITE: Read/Write
Address (in HEX): 2007
8. Variable - SP4
Description: Set point 4
Data type: Signed short
Range: spLL to spHL
Decimal dependence: dP
READ/WRITE: Read/Write
Address (in HEX): 2008
InP
1. Variable - SEns
Description: Sensor select
Data type: Unsigned short
Range: 0 - J thermocouple
1 - K thermocouple,
2 - E thermocouple
3 - S thermocouple
4 - B thermocouple
5 - Pt100 RTD
6 - 0-50 mV signal
7 - 0-60 mV signal
8 - 12-60 mV
9 - R thermocouple
Decimal dependence: No
READ/WRITE: Read/Write
Address (in HEX): 2009
2. Variable - IScL
Description: Analog input low
Data type: Signed short
Range: -1999 to Isch
Decimal dependence: dP
READ/WRITE: Read/Write
Address (in HEX): 200A