21
3 oP1
#
6,7
Output 1 to act as:
Range:
1. coP: Controller output
2. tEmP: Temperature
re-transmitted output
3.EsP: Effective Set Point
re-transmitted output
default: tEmP
3 oP1#
1,4,5,8
Output 1 to act as:
Range:
1.coP: Controller output
2.A1no:Alarm 1 normally open
3.A1nc:Alarm 1 normally closed
4.A2no: Alarm 2 normally open
5.A2nc: Alarm 2 normally closed
6.sEnb: Sensor break
7.BrkL: Loop break alarm
8.OFF: Relay off
default: oFF
4
oP2
Output 2 to act as:
Range:
1.coP: Controller output
2.A1no: Alarm 1 normally open
3.A1nc: Alarm 1 normally closed
4.A2no: Alarm 2 normally open
5.A2nc: Alarm 2 normally closed
6.Senb:Sensor break
7.Brkl:Loop break alarm
8.oFF:Relay off
default: oFF
5
oP3
Same as oP2
6 LboP#
5,6,7,8
Loop
break
output
Lbo1#
5,8
: Output 1
Lbo2 : Output 2
Lbo3 : Output 3
default: Lbo2
7
brkt
Break loop time
Range: Off to 9999 s
default: oFF
MAIN MENU:
AL1 (Alarm 1)
Parameter
Description
1
A1tY
Alarm 1 type Range:
1.AbLo: Absolute low
2.Abhi: Absolute high
3.AbbA: Absolute bend
4.dELo: Deviation low
5.dEhi: Deviation High
6.dEBA:Deviation band
7.oPLo: Output low
8.oPhi: Output High
default: AbLo