23
4 AUto
Auto
tuning:
Range:
oFF: auto tuning off
1: auto tuning at every power on
2: auto tuning at first power on
3: Start manually
4: auto tune at every set point
change
default: 2
5 Pb
Proportional
band
Range: 0 to 9999
default: 10
6 Int
Integral
time
Range: OFF to 9999 s
default: 120
7 dEr
Derivative
time
Range: OFF to 9999 s
default: OFF
8 ct#
1,2,3,4
Cycle
time
Range:1 to 130 s
default: 20
9 rs#
1,2,3,4
Manual
reset
Range: 0 to 100.0 %
default: 0
9
rs#
5,6,7,8
Manual
reset
Range: -100.0 to 100.0 %
default: 0
10 hct#
5,6,7,8
heat cycle time
Range: 1 to 130 s
default: 20
11 cct#
5,6,7,8
Cool cycle time, Range: 1 to 130
s
default: 20
12 coeF#
5,6,7,8
Coefficient, Range: 0.1 to 10.0
default: 1
13 cdty#
5,6,7,8
Compressor duty cycle
Range: 0(Off) to 9999 s
default: 0
14 Prmd#
5,6,7,8
Power down mode
Range:
1.cont: Continue
2.rbck: Ramp back
3 rSEt: Reset
default: cont
15 rmP1#
5,6,7,8
Ramp
1
Range: 0.00 to 99.99 - Inf
unit/min
default: Inf
16 Sok1#
5,6,7,8
Soak
1
Range: 0.00 to 99.59 - Inf
hh:mm