10 - TRIMMER ADJUSTMENT
Trimmer
PAUSE
FORCE
Description
Turning clockwise adjusts (increases) the pause time from 3 to 103 seconds.
If adjusted to minimum, automatic closing is disabled.
Turning clockwise adjusts (increases) the motor torque from 25% to 100%. In the first 3 seconds, a
pick-up with 100% power occurs.
Default
Turning clockwise adjusts (increases) the run time from 2 to 103 seconds.
RUN
TIME
Turning clockwise adjusts (increases) the closing delay time of leaf 1 with respect to leaf 2 from 0 to
20 seconds. The phase shift during opening is fixed at 2 seconds.
Set to minimum, the delays during both opening and closing will be cancelled (version with 2 sliding
gates with consequent deactivation of the water hammer).
P.S.
TIME
DESRCIZIONE MENU ( A )
11 - FINAL CHECKS
Before powering the control unit, proceed with the following checks:
Ÿ
Check the electrical connections; improper connection may be harmful to both the control unit and the operator.
Ÿ
Check that the limit switches (if used) are in the correct position.
Ÿ
Always provide for mechanical stops during opening and closing
Ÿ
Adjust the RUN TIME trimmer setting the desired run time (up to maximum 103 seconds turning clockwise).
Ÿ
Adjust the P.S. TIME trimmer setting the desired phase shift time.
Ÿ
Adjust the PAUSE trimmer setting the desired pause time (up to maximum 103 seconds turning clockwise).
Ÿ
Set the DIP switches for the desired operation.
Ÿ
Power the device.
Ÿ
Check that the red LEDs of the N.C. contacts are on and the green LEDs of the N.O. contacts are off.
Ÿ
Check by tripping the limit switches (if used and enabled with the appropriate DIP switches) that the corresponding LEDs go off.
Ÿ
Check by passing through the photocell beam (if used and enabled with the appropriate DIP switch) that the corresponding
LED goes off.
Ÿ
Check that the motors are locked and ready for operation with the GATE AT HALFWAY ITS TRAVEL.
Ÿ
Remove any obstacles in the range of action of the gate and then give a START command.
Ÿ
Upon the first command, the control unit starts an opening phase; check that the gate moves in the correct direction. If not, cut
the power to the control unit and invert the wires of terminal M1 (position 1-3 for motor 1 and 4-6 for motor 2). Repower the
control unit and give a START command.
Ÿ
During motion, turn the FORCE trimmer anticlockwise until finding the desired force/speed value.
Ÿ
Check proper functioning of the automated device.
9 - DIP SWITCH DIP2
DIP2_3
DIP2_4
NOT USED