HD50CR
- 40 -
V1.0
Address Type
Holding Register description
10035
W
RS485 communication mode:
0=8N1, 1=8N2, 2=8E1, 3=8E2, 4=8O1, 5=8O2
10036
W
Password to be supplied to enable configuration change commands. The
reading provides the fixed value 32768.
da 10037
a 10046
B
Device group with ASCII codification.
Acceptable values are in the set {32,…,126}.
10049
W
Differential pressure unit of measurement: see the table of indexes
10052
W
Setting of the quantities to be displayed in the automatic viewing cycle.
Set the i-th bit (starting from LSB) to 1 if you wish to include the i-th
quantity in the viewing cycle.
Example: if 1=Temp., 2=RH, 3=Td, 4=Diff.Press., 5=Atm.Press., 6=AH,
7=Tw, the register is set to 0000 0000 0010 0010, only the relative hu-
midity (RH) and the absolute humidity (AH) will be displayed alternatively.
10064
W
Modbus address
10065
W
Buzzer silencing time, in minutes, for the quantity #1
10066
W
Buzzer silencing time, in minutes, for the quantity #2
10067
W
Buzzer silencing time, in minutes, for the quantity #3
10068
W
Buzzer silencing time, in minutes, for the quantity #4
10069
W
Buzzer silencing time, in minutes, for the quantity #5
10070
W
Buzzer silencing time, in minutes, for the quantity #6
10071
W
Buzzer silencing time, in minutes, for the quantity #7
10077
B
Current range of the analog output 1: 0=0…20 mA, 1=4…20 mA
10078
B
Voltage range of the analog output 1: 0=0…10 V, 1=0…5 V
10079
SW Value of the quantity associated with the analog output 1 corresponding
to 0/4 mA and 0 V
10080
SW Value of the quantity associated with the analog output 1 corresponding
to 20 mA and 5/10 V
10081
W
Analog output 1 test register: the current output goes to the value, in
tenths of mA, entered in the register (e.g., enter 120 for 12.0 mA).
Set -1 to exit the test mode.
10082
W
Analog output 1 test register: the voltage output goes to the value, in
tenths of V, entered in the register (e.g., enter 50 for 5.0 V).
Set -1 to exit the test mode.
10083
B
Current range of the analog output 2: 0=0…20 mA, 1=4…20 mA
10084
B
Voltage range of the analog output 2: 0=0…10 V, 1=0…5 V
10085
SW Value of the quantity associated with the analog output 2 corresponding
to 0/4 mA and 0 V
10086
SW Value of the quantity associated with the analog output 2 corresponding
to 20 mA and 5/10 V
10087
W
Analog output 2 test register: the current output goes to the value, in
tenths of mA, entered in the register (e.g., enter 120 for 12.0 mA).
Set -1 to exit the test mode.
10088
W
Analog output 2 test register: the voltage output goes to the value, in
tenths of V, entered in the register (e.g., enter 50 for 5.0 V).
Set -1 to exit the test mode.
10089
B
Current range of the analog output 3: 0=0…20 mA, 1=4…20 mA
10090
B
Voltage range of the analog output 3: 0=0…10 V, 1=0…5 V
10091
SW Value of the quantity associated with the analog output 3 corresponding
to 0/4 mA and 0 V
10092
SW Value of the quantity associated with the analog output 3 corresponding
to 20 mA and 5/10 V
Summary of Contents for Delta OHM HD50CR