Data Aire unit. To determine the model number, locate the product description label on the
Nortec humidifier. Match the model number to the table below to determine the amount of steam
generated. All humidifiers can be adjusted within the range minimum to 100%. Factory setting
is 60% of capacity.
Question 5: Is an air vent valve required in the piping when an expansion tank is used? Answer:
Yes, air vents must be installed in various locations in the piping system to purge air and are
required at the highest point in the piping system. One of the most common problems in
water/glycol systems is the presence of air in the condenser loop. In addition, an expansion tank
is recommended on glycol systems. See section
2.19 Water/Glycol Cooled Unit Piping
information.