03 Fire Door Control Systems
28
Fire Control Panel 03 – Engineers Set Up
5. SAFETY CIRCUIT (Only if Door Type = Full Control)
Closing Style Full Drop – Off or On
Closing Style 2 Stage Drop – Both, Full, Part or Ignore
If a Photo Beam is installed this setting controls the response of the shutter during powered
Alarm operation.
Closing Style Full Drop
OFF
The Photo Beam does not stop the Shutter from closing.
ON
If the Photo Beam is obstructed during powered Alarm close operation the Shutter will stop.
Further Options become available when this is set ON. See below **
Closing Style 2 Stage
BOTH
If the Photo Beam is obstructed during either Stage 1 part close or Stage 2 full close powered
Alarm sequence the Shutter will stop.
FULL
If the Photo Beam is obstructed during Stage 2, full close, powered Alarm sequence the Shutter
will stop. The Photo Beam does not stop the Shutter during Stage 1 part close sequence.
PART
If the Photo Beam is obstructed during Stage 1, part close, powered Alarm sequence the
Shutter will stop. The Photo Beam does not stop the Shutter during Stage 2 full close sequence.
Further Options become available when this is set BOTH, FULL or PART. See below **
IGNORE
The Photo Beam does not stop the Shutter from closing.
**SUB MENU OPTIONS (Only if Safety Circuit = ON, BOTH, FULL or PART)
5a. NO OF RETRIES
During an Alarm if the Photo Beam is continuously obstructed the FCP03 can be programmed
to ignore the Photo Beam after checking “x” times to see if the obstruction has been removed.
For unlimited retries set the number of retries counter to 000.
5b. PAUSE LENGTH – MINS, SECS
During an Alarm obstructing the Photo Beam stops the Shutter, it will try to close again after the
time set by the “Pause Length”. The pause length is set in minutes and seconds.
5c. REOPEN – Off or On
OFF
After the Pause Length Time the Shutter continues to close.
ON
After the Pause Length Time the Shutter reopens for the time set “REOPEN TIME”
5d. REOPEN TIME – MINS, SECS
The Reopen Time is set in minutes and seconds
Options 5, 5a, 5b, 5c and 5d are not displayed if Door Type Solenoid Drop is selected.
If Door Type Full Control is set and the Mains Power has failed the Alarm Solenoid is
energized and the Shutter will close by Gravity. Obstructing the Photo Beam will not stop
the shutter.