03 Fire Door Control Systems
27
Fire Control Panel 03 – Engineers Set Up
1. DOOR TYPE - Solenoid Drop or Full Control
Solenoid Drop
When an Alarm is raised the Fire Shutter Alarm Solenoid is energized and the Shutter closes by
controlled Gravity descent.
Full Control
If Mains Power is on when an Alarm is raised the Shutter closes by powered operation. (Normal
motor driven)
If Mains Power has failed when an Alarm is raised the Fire Shutter Alarm Solenoid is energized
and the Shutter closes by controlled Gravity descent.
2. CLOSING STYLE (Only if Door Type = Full Control) – 2 Stage Drop or Full Drop
2 Stage Drop
The Fire Shutter closes to a set height on activation of Zone 1 Alarm, closing completely on
activation of Zone 2 Alarm.
If Zone 2 Alarm is activated before Zone 1 closing to the Zone 1 position is carried out before
the Zone 2 complete closing.
This option is not displayed if Door Type Solenoid Drop is selected.
Full Drop
The Shutter closes in one drop.
3. DOUBLE (KNOCK) NOC (Only if Closing Style = Full Drop) – Off or On
OFF
Ignores the Double Noc Option.
ON
Alarm Zones 1 & 2 must both be triggered before the FCP03 will activate the Alarm closing
Sequence.
If only one of the Zones triggers the AUX 1 relay is energised.
This option is not displayed if Closing Style 2 Stage Drop is selected.
4. SAFETY CIRCUIT-HUNTING - Ignore or Stop
If a Photo Beam is installed this setting controls the response of the shutter during normal push
button / key switch powered operation.
IGNORE
The Photo Beam does not stop the shutter during normal powered close operation.
STOP
If the Photo Beam is obstructed during normal Push Button / Key Switch powered close
operation the Shutter will stop.
The Shutter will continue to close when the Photo Beam is clear of obstruction and a Close
Push Button / Key Switch is operated.