03 Fire Door Control Systems
33
Fire Control Panel 03 – Trouble Shooting
Fault Indication
The LED’S and the Alphanumeric
display are off.
The Mains Supply and Batteries
are disconnected.
The ribbon cable from the front
cover to the main PCB is
disconnected.
Mains LED is Off, Fault LED On,
Sounder bleeps every 10 seconds.
Mains Supply Off
Set LED flashes rapidly
The panel has not been Reset after
an Alarm.
The FPC03 Lamp does not flash
when pressing the buttons to enter
Set-up, Engineering mode.
Batteries are not connected.
Fault Finding
The Motor will not run.
Check the Motor Supply.
Check the Motor Safety Circuit, i.e.
Manual Operator, Over travel
Limits, Motor Thermal.
FCP03 Stop Circuit, terminal 3 – 5,
is closed.
Check FCP03 Fuse F4.
The Alarm Solenoid will not
operate, Shutter does not close in
Alarm
Check that the FCP03 is set to:
Door Type = Solenoid Drop.
Check Fuse F7.
The FCP03 and Shutter do not
operate by Alarm.
Check Fuse F8