background image

8850-2 Conductivity/Resistivity Transmitter 

3.1  Sensor Input Connections

14 
13 
12 
11 

Shield (Sensor Gnd)
Black (Iso Gnd)
White (Temp In)
Red (Signal In)

Signet 28XX-1 

Standard and Certified Cells 

Terminals 

Signet  

Conductivity/Resistivity 

Transmitter 

ENTER

62.50 uS/cm

25.0 C

”PIW

4

3

2

1

14

13

12

11

10

9

8

7

6

5

System Pwr

Loop -

System Pwr

Loop +

AUX

Power - 

AUX

Power +

Sensr Gnd

(SHIELD)

Iso. Gnd

(BLACK)

Temp. IN

(WHITE)

Signal IN

(RED)

Relay 2

(NO)

Relay 2

(COM)

Relay 2

(NC)

Relay 1

(NO)

Relay 1

(COM)

Relay 1

(NC)

3. Electrical 

Connections

Caution:

 Failure to fully open terminal jaws before removing wire may permanently damage instrument.

Wiring Procedure

1.  Remove 13 to 16 mm (0.5 to 0.625 in.) of insulation from wire end.
2.  Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
3.  Insert exposed (non-insulated) wire end in terminal hole until it bottoms out. 
4.  Release orange terminal lever to secure wire in place. Gently pull on each wire to ensure a good connection.

Wiring Removal Procedure

1.  Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
2.  When fully open, remove wire from terminal.

Wiring Tips:

•  Do not route sensor cable in conduit containing AC power wiring. Electrical noise may interfere with sensor signal.
•  Routing sensor cable in grounded metal conduit will help prevent electrical noise and mechanical damage.
•  Seal cable entry points to prevent moisture damage.
•  Only one wire should be inserted into a terminal. Splice double wires outside the terminal.

2
1

Terminals 5-10: Relay Outputs

Two SPDT mechanical relays, programmable as:

•  High or Low setpoint with adjustable hysteresis.
•  Proportional Pulse (400 pulses per minute maximum).
•  May be disabled (Off) if not used.

Terminals 11-14: Sensor input

11 is conductivity input
12 is temperature input
13 is the isolated signal ground
14 is the sensor earth ground

Terminals 1-2: Auxiliary power

Provides DC power to measurement circuit. 
Required for all 8850 systems.

Cable length is limited to 7.5 m (25 ft.) 
where the operating range is above 10M

Ω

.

Terminals 3 and 4: Loop Power

12-24 VDC ±10% system power 

and current loop output.

Max. loop impedance:

  50 

Ω

 max. @ 12 V

325 

Ω

 max. @ 18 V

600 

Ω

 max. @ 24 V

Summary of Contents for Signet ProcessPro 8850-2

Page 1: ...nder ISO 9001 and ISO 14001 CAUTION Remove power to unit before wiring input and output connections Follow instructions carefully to avoid personal injury Contents 1 Installation 2 Specifications 3 El...

Page 2: ...val Procedure 1 Press the orange terminal lever downward with a small screwdriver to open terminal jaws 2 When fully open remove wire from terminal Wiring Tips Do not route sensor cable in conduit con...

Page 3: ...Loop AUX Power AUX Power Transmitter 2 Terminals PLC Terminals Loop Input 4 20 mA Transmitter Terminals System Pwr Loop System Pwr Loop AUX Power AUX Power Power Supply 12 24 VDC Power Supply 12 24 VD...

Page 4: ...keys The selections will scroll in a continuous loop Changing the VIEW display does not interrupt system operations No key code is necessary to change display selection Output settings cannot be edite...

Page 5: ...2 The Key Code is keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with or arrow keys Step 4 Press key to select menu item to b...

Page 6: ...ut Loop Range S 0 0000 100 00 Select the minimum and maximum values for the 4 to 20 mA current loop output Be sure to modify this setting if you change the Cond Units Relay1 Source Cond Select Conduct...

Page 7: ...able display and output response Temp Display C Select temperature units C or F Temperature Comp 2 00 Set the percent change in Conductivity caused by a 1 C change in temperature May be from 0 00 to 1...

Page 8: ...t value If the instrument does not display the correct value Temperature 0 5 C Conductivity 2 of reading service is required A Accuracy Verification with Precision Resistors Electronic Calibration 1 S...

Page 9: ...ayed temperature and conductivity values in the spaces provided Displayed temperature T1 _______ C Displayed conductivity C1 _______ S 3 Cool the sample solution close to the minimum process temperatu...

Page 10: ...condition if your process operates at or near the limits of the electrode range Check sensor for correct range Check Decimal setting in OPTIONS menu Check Calibrate menu settings for incompatible SOUR...

Page 11: ...11 8850 2 Conductivity Resistivity Transmitter Notes...

Page 12: ...085 CR Sanitary 0 01 SS 1 to 1 1 2 in 3 2819 S1C 159 000 087 CR Sanitary 0 01 SS 1 to 1 1 2 in Certified 3 2819 S2 159 000 086 CR Sanitary 0 01 SS 2 in 3 2819 S2C 159 000 088 CR Sanitary 0 01 SS 2 in...

Reviews: