6
Signet 2580 FlowtraMag Meter
Wiring Confi guration
When using the 2580 with frequency or Digital (S
3
L), all of the
connections from the Magmeter to external equipment (PLC,
Datalogger, Chart Recorder, Flow meter, etc.) are made using the
red and white wires. See wiring diagrams for further details.
Recommended:
The directional arrow should be pointed
DOWNSTREAM
for correct operation. Use a cable
gland or a liquid tight connector to seal the cable
ports from water intrusion. If the 2580 is installed
on a vertical pipe, the cable ports should be turned
to point downward. This will prevent condensation
from being channeled into the enclosure.
3-2580
Black
Red
White
Red
Power cable
Output cable
Shield
Black
Brown
Shield
Blue used for
GF Config App password
reset only
S
3
L / Frequency
4 to 20 mA
Application Tip:
If your fl ow is in the reverse direction, it is
possible to set up reverse fl ow via the
Signet 0252 Confi guration Tool or
GF Confi g Tool App.
1"
2"
4"
Units
GPM
GPM
GPM
Totalizer Units
Gallons
Gallons
Gallons
Temperature Units
°C
°C
°C
K-Factor Values
852.716 pulse/gal 204.139 pulse/gal 52.1188 pulse/gal
Averaging
Low
Low
Low
Sensitivity
3.5182
14.696
57.561
Low Flow Cutoff
0.1407
0.5878
2.3024
4 mA Setpoint
0
0
0
20 mA Setpoint
70.363
293.92
1151.2
Error Current
22
22
22
Passive/Active
Passive
Passive
Passive
S3L/Freq
Freq
Freq
Freq
Default Confi gurations
DO NOT REMOVE WIRING!
Damaging or removing the power or
output cables will void warranty.