Signet 0250 Setup Tool

AVERAGING Only

With AVERAGING set to 60 seconds and SENSITIVITY set to 
100%, the fl ow rate is stabilized, but a sharp change in fl ow rate 
is not represented for 60 seconds or longer. This can cause 
system problems if one of the operating setpoints falls within this 
range.

AVERAGING and SENSITIVITY

With AVERAGING at 60 seconds and SENSITIVITY set to 25%, 
the fl ow rate is stabilized, but the sudden shift in fl ow is refl ected 
very quickly.

No AVERAGING, no SENSITIVITY

With AVERAGING set to 0 (zero) the SENSITIVITY is ineffective, 
and the fl ow rate may be very unstable.  This will cause the output 
signals to respond erratically.

10 s

20 s

30 s

40 s

50 s

60 s

70 s

Time

V

e

locity

10 s

20 s

30 s

40 s

50 s

60 s

70 s

Time

Ve

lo

c

it

y

10 s

20 s

30 s

40 s

50 s

60 s

70 s

Time

V

elocity

Magmeter Averaging and Sensitivity Settings

Because ideal fl ow conditions are often impossible to acheive, the fl ow rate is often erratic, which in turn causes any control features 
(ie; relays, 4-20 mA loops, etc.) that are associated with the fl ow rate to also be erratic.

The best solution to these problems is to correct any piping defi ciency that causes the instability. This may involve longer straight runs 
upstream, reducing the pipe size to maintain a full pipe at all times, and other installation changes. In many situations, however, these 
measures are simply not possible.

The Magmeter provides several tools that are designed to "work around" these defi ciencies. They are called "Performance Settings" 
and can be modifi ed only through the 3-0250 Setup Tool. The noise rejection and the Low Flow Cutoff settings are self-explanatory. The 
Averaging and the Sensitivity features should be studied before making adjustments.

Averaging Time in Seconds (Factory set: 14 seconds)

•  Set the time the Magmeter will use as the averaging period.
  With averaging at 14 seconds, each display is an average of the previous 14 seconds input.
  Use higher averaging times to smooth the display and current output where the fl ow in the pipe is erratic.

Quick Response Sensitivity (Factory set: 25% of Maximum Range, or 2.5 m/s)

•  Set the percentage of change in the fl ow rate required to allow the Magmeter to override the AVERAGING and jump to a new fl ow 

rate immediately. (maximum range is 10 m/s)

The pictures below illustrate the effect of these settings.

Summary of Contents for Signet 3-0250

Page 1: ...100 C 4 to 212 F Relative Humidity 0 to 90 non condensing Operating Temperature 15 to 55 C 5 to 131 F module only 3 To run the program from the CD Right click the START button and select EXPLORE Navig...

Page 2: ...setup capability of the 0250 is more complex with the magmeters than with other sensors Read these instructions carefully before attempting to modify a Magmeter CAUTION Do not connect power directly...

Page 3: ...s Set the time the Magmeter will use as the averaging period Example With averaging at 14 seconds each display is an average of the previous 14 seconds input Use higher averaging times to smooth the d...

Page 4: ...exit the program If the settings will be used again click SAVE Name the file and save it on the computer hard drive Read Read and display the existing settings from the Magmeter Write Write from the d...

Page 5: ...atic The best solution to these problems is to correct any piping deficiency that causes the instability This may involve longer straight runs upstream reducing the pipe size to maintain a full pipe a...

Page 6: ...lay into the Magmeter Click Save to save the settings from the display to a computer file 5 To use a saved file Click Load Navigate to the saved file Select Open Click Write Click Read to confirm Sign...

Page 7: ...to the saved file Select Open Click Write Click Read to confirm Signet 2750 pH Sensor Setup 2750 Wiring 2750 Operation 1 Select the engineering units for the application pH or ORP 2 Set the pH or ORP...

Page 8: ...0 seconds the 0250 will record the temperature once every minute The 0250 saves data files in csv format The maximum number of records allowed for this type of file is 65535 If the logging interval is...

Reviews: