F 1200+ window drive
26
Cleaning
11 Cleaning
You will find information about cleaning in the user manual F 1200+ (ID 193469-00).
12 Maintenance
You will find information about maintenance in the user manual F 1200+ (ID 193469-00).
13 Faults
13.1 Eliminating faults
If faults have occurred the LED status display lights up steady yellow until the fault has been eliminated by an
authorised service technician
.
X
If necessary, “emergency-open” or “emergency-close” the window (see chapter 5.7 “Emergency-opening /
emergency-locking of the window”).
X
Put the drive out of operation (see chapter 14 “Decommissioning”).
X
Secure the window unit against triggering (e.g. by means of a sign reading “Out of operation”).
13.2 Table of faults and errors
Number of
the error
Description
Measures
23
Undervoltage detected (at approx. 13 V after
150 ms)
no measures required
26
Blockage at drive start if drive cannot start
moving by 0.1 mm within 3 s
X
Check whether an obstacle blocks window, fitting
or drive and remove obstacle.
27
Drive starts reversal due to a blockage dur-
ing movement
X
Check whether an obstacle blocks window, fitting
or drive and remove obstacle.
X
Test smooth running of the door fitting and lubri-
cate if necessary.
29
Switch-off of motor power stage due to
thermal overload or overcurrent
X
Measure ambient temperature (max. 70 °C) and
reduce if possible.
X
Check duty rating (max. 30 %) and reduce to
maximum value.
39
Overcurrent cut-off
X
Check whether an obstacle blocks window, fitting
or drive and remove obstacle.