INSULATION DISTANCE
Breaker
A
Note
B1
B2
C
D
E
MSX/M 160c
50
50
10
* Possible to set close
25
Not less than the length of the bare live part Note
MSX/M 250c
50
40
40
* Possible to set close
50
Not less than the length of the bare live part Note
Tables of insulation distances
Notes:
The figures are for lower breakers.
For front connection breakers, insulate all exposed conductors of the line side until the breaker end. If interpole barriers are packed, be sure to use the barriers; more over, insulate all exposed
conductors by insulating tape or the like so that the tape overlaps with the barriers.
* If using extension bars (optional), ensure the insulation distance specified for the application.
DIRECTION OF POWER SUPPLY
The breakers are available for normal connection by default. Reverse connection is optional.
See tables below.
Line side
Line side
Load side
Load side
Normal
connection
Reverse
connection
MSX
80
COMPACT MCCB WITH THERMAL-MAGNETIC PROTECTION
AND COMPACT SWITCH-DISCONNECTORS
MSX/M 160c - MSX/M 250c
Technical Information
Version 2.0