MOTOR OPERATOR
Manual Operating Handle
Indicator
Lock Plate
Trip Button
Motor operators for MCCBs 1250A and 1600A
Ratings and Specifications
MCCB frame
1250A - 1600A
MCCB model
MSXE/M 1250
MSXE/M 1600
Lock in “OFF” position (standard)
Manual Trip Button
Operating current/
Inrush current (A)
230-240V c.a.
ON
–/1.2
OFF, RESET
1.0/3.2
24V c.c.
ON
–/4.5
OFF, RESET
4.0/12.0
Type of operation
Spring Charged
Operating Time(s)
ON (Maximum values)
0.06
OFF, RESET
3
Control Switch Ratings
250V, 5A
Power Source Capacity (VA)
300VA
Dielectric withstand voltage
The value in brackets for 24V DC
AC1500V
(AC500V)
Weight (kg)
6.4
NOTE
Maximum values at AC230V, 50Hz
Maximum values at the rated operating voltages
The breaker can be padlocked in the
“OFF” position by pulling out the lock
plate, and locking it with a padlock.
When the breaker is “ON”, the
lock plate cannot be pulled out.
Up to three lock can be used.
Padlock not supplied.
Positive Contact Indication
• Colour coding indicates the true position of the contacts clearly:
ON (red), OFF (green), TRIP (white).
Easy Maintenance
• Breaker mounting, removal, and even setting changes can be done
without removing the motor operator.
Manual ON/OFF Operation with One Stroke
Fast Closing Operation
• Closing in 60ms or less.
The closing time remains constant over repeated operations.
MSX
58
Informazioni Tecniche
Versione 2.0
Per informazioni tecniche contattate il SAT o visitate il sito gewiss.com
MCCB WITH THERMAL-MAGNETIC, ELECTRONIC, RESIDUAL CURRENT PROTECTION
AND SWITCH-DISCONNECTORS
MSX - MSXD - MSXE - MSXM