ACCESSORIES AND CONNECTION/MOUNTING OPTIONS
Connection (one electric cable)
If a shortage of insulating
occurs, use recommended
tape or insulator.
Make connection so that the screw
heads face toward the
mounting surface.
If a shortage of insulating
occurs, use recommended
tape or insulator.
Make connection so that
the screw heads face toward the
mounting surface.
If a shortage of insulating occurs
between the mounting plate and
a terminal, use a recommended
taping or insulator.
When a single
terminal is
connected
Second terminal
when two terminals
are connected
Connection (two electric cables)
Connection (two terminals)
Crimp lugs types
Each terminal on 250A models has a serrated surface. This provides excellent grip for heavy cables terminated with crimp lug terminals, thereby preventing
sideways rotation of the lug.
Maximum dimensions of crimp lug
Frame Size (A)
160
250
Width, W (mm)
17.2
25
Diameter, d (mm)
8.5
9
Maximum from centre to tip, e(mm)
9.5
11
Connection of cables terminated with crimp lugs
MSX
78
COMPACT MCCB WITH THERMAL-MAGNETIC PROTECTION
AND COMPACT SWITCH-DISCONNECTORS
MSX/M 160c - MSX/M 250c
Technical Information