Alarm threshold temperature setting
Use the
or
button key to set the floor temperature limit above
which the timed thermostat blocks heating to prevent any damage
(value expressed in tenths of a °C, can be set between 150 and 1000,
with steps of 100). The parameter is only displayed if the NTC
temperature sensor connected to the timed thermostat is enabled
as a temperature probe (TEMP).
To confirm your choice and move on to the next parameter, press
the
button key within 30 seconds.
Local relay setting
Use the
or button key to set the operating mode of the timed
thermostat relay (OFF = disabled, HEAT = heating valve
management, COOL = air conditioning valve management,
BOTH = heating/air conditioning valve management).
To confirm your choice and move on to the next parameter, press
the
button key within 30 seconds.
Operating parameters
Selecting Heating or Air conditioning
Use the
or
button key to select the operating type
(
= heating;
= air conditioning). To confirm your choice
and move on to the next parameter, press the
button key within
30 seconds.
If the operating type is "heating":
Setting the set-point
(heating) /
Used to modify the temperature value associated with the
set-point (if the page visualised relates to the timed
thermostat), or the Value 1 of the hourly profile associated
with the status
(if the page visualised relates to the
hourly timer). Adjust the value of
(T
ECONOMY
) /
with the aid of the
button keys. To confirm the set
value, press the
button key within 30 seconds.
USER INSTRUCTIONS
E
N
G
L
I
S
H
17
Summary of Contents for Chorus GW 10 764
Page 2: ......