Installation
Note:
Follow the instructions for the host device.
Avoid damp environments and extreme temperatures (Fig. 3). Note that
metal surfaces and walls containing metal can severely dampen or
reflect the radio signals (Fig. 4). Maintain a minimum distance of one
metre between the radio modules (Fig. 5) during installation. Maintain
a minimum distance of one metre from large appliances (Fig. 6).
• Follow the instructions for the host device when determining the
installation location.
• Plug the three-pin terminal of the radio module (Fig. 1.3) onto the
underside of the device (Fig. 2).
• Close the lid of the device. (Special feature of smoke detectors:
If a battery is not inserted into the smoke detector, it is not
possible to lock the smoke detector in place on the radio
module.)
Note:
Make sure that the connection wires are not
routed over the circuit board of the radio module —
instead, they must be routed directly from the edge of
the housing to the three-pin plug on the radio module
• Once all radio modules/host devices are installed, perform a
function test for example by pressing the test button on the
smoke detector until the smoke detector emits alarm sounds
or provoke a false alarm. (When performing the function test,
follow the instructions for the host device.) The radio modules/
or the devices equipped with it of the same radio group signal
the alarm acoustically and automatically return to normal mode
after a short period of time. If a detector forwards the OUT
signal, it acknowledges that it has done so by emitting three
short sounds. See the section entitled „Operation/testing“.
The device is approved for operation inside the European
Community.
GEV GmbH hereby declares that this device (Radio Transmit
and Receive Module FMF 3545) accords with the fundamental
requirements and the other relevant regulations of guideline
1999/5EG. The full declaration of conformity can be seen under:
www.gev.de
Recycling guidelines:
This device must not be disposed of as unsorted household
waste. Used devices must be disposed of correctly. Contact
your local town council for more information.
Technical data:
Type designation
FMF 3545
Frequency
0 - 868 MHz
Operating voltage
9 V from the host device
Working temperature range
0 - 40°C
Relative humidity
0 - 90% non-condensing
Dimensions
Ø 106 mm, height 12 mm
Colour
white
Technical and design features may be subject to change.
BA_3545_MA00822802_04062018_DIN_A6.indd 12
06.06.2018 12:16:03
Summary of Contents for FlammEx FMF 3545
Page 1: ...03545 FMF 3545 BA_3545_MA00822802_04062018_DIN_A6 indd 1 06 06 2018 12 16 00 ...
Page 2: ...1 2 1 2 3 9V 9V 9V 9V 9V 9V 9V BA_3545_MA00822802_04062018_DIN_A6 indd 2 06 06 2018 12 16 00 ...
Page 3: ...3 4 BA_3545_MA00822802_04062018_DIN_A6 indd 3 06 06 2018 12 16 01 ...
Page 4: ...5 25 m 1 m BA_3545_MA00822802_04062018_DIN_A6 indd 4 06 06 2018 12 16 01 ...
Page 5: ...6 1 m BA_3545_MA00822802_04062018_DIN_A6 indd 5 06 06 2018 12 16 01 ...
Page 19: ...19 GB FR IT DE BA_3545_MA00822802_04062018_DIN_A6 indd 19 06 06 2018 12 16 03 ...