55
NRG 26-61 - Installation & Operating Manual -
819874-00
System malfunctions
The display or control unit reacts to changes of level too slowly or too quickly.
Possible causes if no error messages appear
Remedy
The damping coefficient “FiLt” is incorrectly
set.
Correct the damping coefficient “FiLt”.
The equipment fails to work. No display and the LEDs do not light up.
Possible causes if no error messages appear
Remedy
Supply voltage failure.
■
■
Switch on the supply voltage.
■
■
Check all electrical connections.
The equipment fails to work. The display is on and the LEDs light up.
Possible causes if no error messages appear
Remedy
The earth connection to the tank is interrupted.
■
■
Clean the sealing surfaces and
■
■
screw in the level electrode with a metal sealing ring,
see page 27.
Flashing values from t-71 to t-75 appear on the display
Possible causes
Remedy
The ambient temperature of the electrode terminal box
is high, between 71 °C and 75 °C.
If the temperature rises above 75 °, the fault
code E.027 (Overtemp Err) appears and a plant
shutoff occurs.
■
■
Reduce the ambient temperature around the terminal
box, e.g. by cooling.