51
NRG 26-61 - Installation & Operating Manual -
819874-00
System malfunctions
Causes
System malfunctions occur if CAN bus components have been incorrectly installed or configured, if the
equipment has overheated, if there is interference in the supply network or if electronic components are
faulty.
Check the installation and configuration before systematic troubleshooting!
Installation:
■
■
Check that the installation location complies with the admissible ambient conditions in terms of
temperature, vibration, interference sources, minimum distances, etc.
Wiring:
■
■
Does the wiring conform to the wiring diagrams?
■
■
Is the bus line polarity correct throughout?
■
■
Is a 120 Ω terminating resistor connected to the terminal devices of the CAN bus line?
Configuration of the level electrode:
■
■
Is the level electrode set to the correct limiter ID 1,2,3,4,5,6,7,8?
■
■
Limiter IDs must not be assigned in duplicate.
Baud rate:
■
■
Is the cable length correct for the set baud rate?
■
■
Is the baud rate identical for all units?
ATTENTION
Interrupting the CAN bus causes a plant shutdown and triggers an alarm.
■
■
Bring the plant into a safe operating state before commencing work on the installation.
■
■
Switch off the voltage to the plant and secure so that it cannot be switched back on.
■
■
Check that the plant is not carrying live voltage before commencing work.