NRG 26-61 - Installation & Operating Manual -
819874-00
Bringing into service
Before bringing into service, check that all equipment is correctly connected:
■
■
Is the polarity of the CAN bus control line correct throughout?
■
■
Is a 120 Ω terminating resistor connected to the terminal devices of the CAN bus line?
Next, switch on the supply voltage.
Changing the factory settings if necessary
You will need the following tools
■
■
Slotted screwdriver, size 2.5
Notes for bringing into service for the first time
When the equipment is brought into service for the first time, the “
AL.Lo”
and “
AL.Hi
” alarm
limits are set to Max/Min values, which is why the warning messages “
LO.LE
” and “
HI.LE
” are
shown alternately on the display.
First, set the “
AL.Lo
” and “
AL.Hi
” alarm limits to suitable values for your specific plant,see
page 42.
Measuring range calibration and the setting of alarm limits are mutually independent.