background image

But there’s internal protection so that no step is re-connected before 45-50 seconds since this period is required for the capacitor unit 
to discharge. Otherwirse there’ll be over voltages on the capacitor unit which wiill cause damages.

In the same logic, no step is connected before 45-50 seconds if the supply voltage (system voltage) is off and on again.

In the switching logic, the amount of the reactive power required as well as the rotating system logic are also important . The relay 
will decide to connect or disconnect  the proper step according to the power required.

OVER and UNDER VOLTAGE PROTECTION

If the supply voltage exceeds an adjusted value between 250 Volt and 299 Volt, the “O.V.set” led will start blinking.  İf the over 
voltage continues longer than 2-3 seconds, the relay will disconnect all steps. And the display will read “

A G r

” blinking meaning that 

there was over voltage.
If the supply voltage is approximately  5V below the set value, “

A G r

” will be cleared and the display will start reading the present 

co s ø

 value.The relay will start to operate properly  and if necessary, it’ll start to connect the capacitor stpes.

If the supply voltage is below 160 Volts, all steps are disconnected automatiically and the display will read  “

d gr

” meaning under 

voltage
If the supply voltage is over 165 Volts again,”dgr” will disappear on the screen and  the present 

co s ø

 value will start reading on the 

display. The realy will start to operate properly and if necessary, it’ll start to connect the capacitor steps.

AUTOMATIC POLARITY ADJUSTMENT :

In case the terminals “k” and “l” of the current transformer are not connected in the proper sequence , the relay will sense and 
corrects this mistake .
But it’s important to connect the supply voltage and the current transformer from the same phase of the network. 

If the supply voltage and the current transformer are at different phases, the polarity adjustment will not operate and the 
relay will not function properly since the input datas are not correct.

ALARM:

If normal led is off within 5 minutes after all capacitors are in operation or  all capacitors are disconnected, that means a problem with 
compensation. In this case,  “

Alr

” is displayed and starts blinking . At the same time, alarm relay operates, and alarm contacts will 

function. After the system becomes normal, “

Alr

”  is cleared on the screen and 

co s ø

 value is displayed again. 

CONNECTION AND COMMISSIONING :

The connection of the relay is at Figurel 2. As a sample, 7-step relay connection is included in the figure. Every relay has its own 
connection diagram at the rear panel .

The important points for the connection are as follows;
The voltage supply and the current transformer should be on the same phase. In case the voltage supply and CT phase don’t match, 
the cosø value on the display will be wrong and the relay will not function properly..

The current transformer should be connected at the load before the capacitor units, the CT current should read both the load and 
capacitor currents.

The phase voltage should be connected to the terminal no.2 of the relay via 6A fuse, the neutral of the supply voltage should be 
connected to terminal no.1 on the relay . 

As described in the Setting section, , “

c/k

” , “Set

 C o s ø

” , “

T

on

” , “

T

off

” , “Steps, ” “

S e q u e n c e

” and  “O.V.set”  values are adjusted 

properly. If 

C/k

 set is at automatic setting, the relay will choose the proper c/k and start to function.

In case  

c/k

 set value is to be adjusted manually, please use selection Table 1. 

Even the factory setting are not changed, in most cases the result and functionality is successfull.  In case the load is variable, too 
low , too much, it’s advised to choose sequence  1.2.3.6........6 or  1.2.4.8...........8 for beter results. 

TECHNICAL PROPERTIES

Summary of Contents for RQ B Series

Page 1: ...number of steps 6 different sequence logic Reactive Active power ratio is displayed on the screen Under voltage over voltage and compensation failed alarms Easy programming Harmonic free operation Eas...

Page 2: ...0 99 with 0 01 steps 3 Ton re connect delay setting Press Set button until T on led is on Adjust T on to the desired value using up and down buttons Press Set button again T on will be stored in the m...

Page 3: ...ll operate automatically within 10 seconds as programmed Relay has 6 different sequence logic a 1 1 1 1 1 1 system displayed as 1 1 1 b 1 2 2 2 2 2 system displayed as 1 2 2 c 1 2 3 3 3 3 system displ...

Page 4: ...ed is on means the load is inductive Cos led is on displaying the present cos power factor Q P led is on displaying the present ratio of reactive power to active power For example the display reading...

Page 5: ...current transformer from the same phase of the network If the supply voltage and the current transformer are at different phases the polarity adjustment will not operate and the relay will not functi...

Page 6: ...teps are disconnected for no voltage more than 50 msec c k set 0 03 1 15 or automatic c k set Set Cos 0 90 0 99 Sequences 1 1 1 1 1 2 2 2 1 2 3 3 1 2 4 4 1 2 3 6 6 1 2 4 8 8 Contacts Same as number of...

Page 7: ...03 0 06 0 12 0 18 0 25 0 31 0 37 0 5 0 62 0 75 500 5 0 05 0 1 0 15 0 2 0 25 0 3 0 4 0 5 0 6 1 600 5 0 04 0 08 0 12 16 0 2 0 25 0 33 0 41 0 5 0 83 800 5 0 03 0 06 0 09 0 12 0 15 0 18 0 25 0 31 0 37 0...

Page 8: ...Q 1 1 2 B R e a k tiv e P o w e r C o n tro l R e la y set k C 144 70 90 138 138 Panel window with 144 v v v v v v v v v v v v GEPA K o m p a n z a s y o n c H e d e f c o s T K a d s a y s S ra la m...

Page 9: ...T K a d s a y s S ra la m a A G a y a r M a n u e l o n T o ff N o rm a l C C a p In d 1 2 3 4 5 6 7 8 9 10 11 12 Q P c o s R Q 1 1 2B R e a c tiv e P o w e r C o n tro l R e la y set k C R Q B S E R...

Reviews: