In case no additional buttons are pressed , the relay will operate automatically within
10 seconds as programmed..
C/k is adjustable between 0,03 and 1,15 with 0,01 steps
If “
ot o
” is displayed on the screen, c/k was set automatically and the relay will set c/k value by itself automatically.
2-Seting Cosø :
Press Set button until “Set
C o s ø ”
led is on.
Adjust Set
C o s ø
to the desired value using up and down buttons.
Pr e s s S e t
button again, Set
C o s ø
will be stored in the memory and “
T
on
” led will be on.
In case no additional buttons are pressed, the relay will operate automatically within
10 seconds as programmed
S e t C o s ø
is adjustable between 0,90 and 0,99 with 0,01 steps.
3-
T
on
(re-connect delay) setting:
Press Set button until “
T
on
” led is on.
Adjust
T
on
to the desired value using up and down buttons.
Pr e s s S e t
button again,
T
on
will be stored in the memory and
“T
off”
led will be on.
In case no additional buttons are pressed, the relay will operate automatically within
10 seconds as programmed
T
on
(re-connect delay ) is adjustable between 1 and 250 seconds
4-
T
of
f
(re-isolation delay) setting:
Press Set button until “
To ff
” led is on.
Adjust
T
off
to the desired value using up and down buttons.
Pr e s s S e t
button again,
T
off
will be stored in the memory and
“Steps”
led will be on.
In case no additional buttons are pressed, the relay will operate automatically within
10 seconds as programmed
T
off
(re-isolation delay ) is adjustable between 1 and 100 seconds
5-Steps setting:
set
set
set
set
set
set