background image

18

ASTON CONSOLE SERIES INSTALLATION MANUAL

Open Loop Ground Water Systems

Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral 
precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water flow 
through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the 
specification catalog. 1.5-2 GPM of flow per ton of cooling capacity is recommended in open loop applications.

Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, 
i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc.  Most local codes forbid the use of sanitary sewer for disposal.  
Consult your local building and zoning departments to assure compliance in your area.

Note:

 For open loop/groundwater systems or systems that do not contain an antifreeze solution, set SW1-Switch #2 to the   “WELL” 

position

 

(Refer to the Dip Switch Field Selection table). Slow opening/closing solenoid valves (type VM) are recommended to eliminate 

water hammer.

Water Quality

In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop 
system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabili-
ties due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and 
pumping equipment are required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard 
water, the owner should be informed that the heat exchanger may require occasional flushing.

Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corro-
sion, along with reduced wear caused by acid cleaning.

Material

Copper

90/10 Cupronickel

316 Stainless Steel

pH

Acidity/Alkalinity

7 - 9

7 - 9

7 - 9

Scaling

Calcium and

Magnesium Carbonate

(Total Hardness)

less than 350 ppm

(Total Hardness)

less than 350 ppm

(Total Hardness)

less than 350 ppm

Corrosion

Hydrogen Sulfide

Less than 0.5 ppm (rotten egg 

smell appears at 0.5 ppm)

10 - 50 ppm

Less than 1 ppm

Sulfates

Less than 125 ppm

Less than 125 ppm

Less than 200 ppm

Chlorine

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Chlorides

Less than 20 ppm

Less than 125 ppm

Less than 300 ppm

Carbon Dioxide

Less than 50 ppm

10 - 50 ppm

10 - 50 ppm

Ammonia

Less than 2 ppm

Less than 2 ppm

Less than 20 ppm

Ammonia Chloride

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Ammonia Nitrate

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Ammonia Hydroxide

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Ammonia Sulfate

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Total Dissolved Solids (TDS)

Less than 1000 ppm

1000 - 1500 ppm

1000 - 1500 ppm

LSI Index

+0.5 to -0.5

+0.5 to -0.5

+0.5 to -0.5

Iron Fouling

(Biological Growth)

Iron, FE

2

+ (Ferrous)

Bacterial Iron Potential

< 0.2 ppm

< 0.2 ppm

< 0.2 ppm

Iron Oxide

Less than 1 ppm, above this level 

deposition will occur

Less than 1 ppm, above this level 

deposition will occur

Less than 1 ppm, above this level 

deposition will occur

Erosion

Suspended Solids

Less than 10 ppm and filtered for 

max. of 600 micron size

Less than 10 ppm and filtered for 

max. of 600 micron size

Less than 10 ppm and filtered for 

max. of 600 micron size

Threshold Velocity

(Fresh Water)

< 6 ft/sec

< 6 ft/sec

< 6 ft/sec

NOTES:

  Grains = ppm divided by 17

mg/L is equivalent to ppm

2/22/12

Summary of Contents for ASTON SERIES

Page 1: ...15 Installation Information Water Piping Connections Hot Water Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance COMMERCIAL Water Source Geothermal Heat Pump R 410A Refr...

Page 2: ......

Page 3: ...ng 17 Open Loop Ground Water Systems 18 Electrical Connections 19 Electrical Data 20 Auxiliary Heat Ratings 21 Blower Performance 21 Wiring Schematics 22 27 Controls 28 Startup Notes 36 Startup Checkl...

Page 4: ...d Range 6 AlumiSealTM Standard Range 7 No Coating Extended Range 8 No Coating Standard Range Sound Kit A None B Blanket Auxiliary Electric Heat N None B 1 0kW 09 12 C 2 0kW 09 12 D 3 0kW 15 18 Motoriz...

Page 5: ...rom the packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage...

Page 6: ...1 3 3 49 1 11 8 4 3 cm 127 0 31 1 65 2 23 4 88 9 15 6 8 3 124 7 29 8 10 9 09 12 15 18 4 0 5 7 8 1 3 2 6 47 B3 0 193B 47 B3 0 193B 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3 232 B 0 0 19 2 4 B6 C B7 B...

Page 7: ...6 1 2 5 49 1 11 8 4 3 cm 127 0 32 0 73 9 23 4 88 9 15 6 6 4 124 7 29 8 10 9 09 12 15 18 3 D3 AB71 AB 7 4 0 93 B 0 2 3 13 0 93 3253 4 35 A A6 E 6 7 8 1 4 3 2 5 0 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3F...

Page 8: ...15 6 6 1 124 7 30 5 10 9 in 55 0 12 6 29 1 9 2 35 0 6 1 2 5 54 1 11 8 4 3 cm 139 7 32 0 73 9 23 4 88 9 15 6 6 4 137 4 29 8 10 9 09 12 15 18 47 B3 0 193B 47 B3 0 193B 2 3 1 6 7 8 4 0 5 0 756B 3BC B 4 B...

Page 9: ...D32 4 1 7BG 0 B6 A723A 3 31B 71 63 B 23 0 7 3 3AA AE7B16 B7 4 B7 AE7B16 B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 E D B 53 B3 7 A 4F 3 B3 E AB B B7 A G B7 4CA32 4CA32 27A1 31B B7...

Page 10: ...3 25 65 65 2 19 83 50 4 1 64 4 2 12 03 30 6 0 66 1 7 2 75 7 0 5 5 14 0 DAMPER OPENING Models 09 12 BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL 42 88 108 9 34 0 86 4 1 5 3 8 1 5 3 8 4 32 11 0 8 88 22...

Page 11: ...D D3A B7 6 A3 97BA 1 23 A B3 2 7 1 31B7 47 B3 6 2G 0 F B7 3 31B 71 63 B B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 1 B 3 3 D3 4 113AA B 1 B 0 F 2 3 44 AE7B16 1 3AA 113AA 3 3 D32 4...

Page 12: ...PLATE COMPRESSOR ACCESS PANEL DAMPER OPENING 43 37 110 2 1 62 4 1 25 65 65 1 19 83 50 4 Models 09 12 8 88 22 6 34 0 86 4 1 50 3 8 1 50 3 8 4 32 11 0 42 88 108 9 BLOWER ACCESS PANEL COMPRESSOR ACCESS P...

Page 13: ...plate mounting height is increased by the thickness of the shims used Position backplate in desired equipment location To further reduce the operating sound level of the unit 1 8 inch thick rubber mat...

Page 14: ...to the units An air vent must be installed in the water distribution system The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve The...

Page 15: ...es should be installed on both the supply and return water lines of the unit Flow control valves should be installed on the water discharge line It is recommended that P T ports be installed on the su...

Page 16: ...cabinet repositioning pieces 1 2 and 3 into the locations directly opposite the original positions Secure by replacing mounting brackets Note Be sure that louvers on the grille assembly are facing th...

Page 17: ...protect the system from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchange...

Page 18: ...tremely hard water the owner should be informed that the heat exchanger may require occasional flushing Units with cupronickel heat exchangers are recommended for open loop applications due to the inc...

Page 19: ...able 208 Volt Operation All Envision Series 208 230 units are factory wired for 230 volt operation For 208 volt operation the red and blue transformer wires must be switched Microprocessor Remote Ther...

Page 20: ...21 0 2 6 6 7 7 7 10 15 265 60 1 238 292 6 7 4 3 22 0 2 5 6 8 7 9 10 15 12 115 60 1 104 127 14 8 9 5 50 0 4 25 13 8 16 1 25 208 230 60 1 187 253 7 7 4 9 25 0 2 6 7 5 8 8 10 15 265 60 1 238 292 7 0 4 5...

Page 21: ...0 1 239 292 2000 2 50 7 55 10 1 12 6 20 15 18 3 kW 208 60 1 197 254 2454 2 45 11 80 14 3 17 8 30 230 60 1 197 254 3000 2 60 13 04 15 6 19 6 35 265 60 1 239 292 3000 2 50 11 32 13 8 17 3 30 Always refe...

Page 22: ...E 1 T ST CC Compressor Contactor HP High Pressure Switch LP Low Pressure Switch RV Reversing Valve Coil ST Entering Air Temperature Sensor RB Blower Relay Black Black Red 11 Black 12 Red 17 Red 19 Bla...

Page 23: ...Blue Wht 36 Blue Wht 35 White 34 Blue T6 FS Yellow 44 Yellow 44 Brown 43 Yellow 13 Page 1 Blue Tan 41 Blue 40 Blue 40 Brown 3 Tan 41 Brown 26 Green 00 Red 39 Gray 42 NOTE 3 NOTE 4 Violet 4 Violet 4 Vi...

Page 24: ...CCG CC2 HI CC2 LO CC2 G REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPS Aurora Base Control ABC K1 RV Relay K2 CC Relay K3 CC2 Relay K4 Fan Relay K5 Alarm Relay K6 Acc Relay F R C CC G Y1 C R ES LS P2 EH1 Y G G...

Page 25: ...t LED LED3 Red Status LED LED1 Green Normal Mode Control is Non Functional Test Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD 1 second on and 1 second off Random Start Dela...

Page 26: ...ite Yellow Blue Red Black CFM P13 P4 SW1 P5 JW2 P9 LO O B Y2 W DH P8 P7 RS485 NET RS485 NET P6 RS485 EXP P3 SW2 On Future Use L Output Type CC Dual Single Acc Dip 5 Acc Dip 4 RV B O FP2 15 F 30 F FP1...

Page 27: ...Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD 1 second on and 1 second off Random Start Delay Fast Flash OFF ON Slow Flash Fast Flash Flash Code 2 Flash Code 3 Flash Code 6...

Page 28: ...fan speed switch The temperature can be controlled by rotating the thermostat control knob The Fan Only setting provides constant fan operation In the Heat mode a call for heat by the thermostat clos...

Page 29: ...on and 1 second off Additionally when entering test mode LED1 red will flash the last lockout one time Test mode will automatically time out after 30 minutes Test mode can be exited by pressing and ho...

Page 30: ...e turned on The fault type identification display LED1 Red shall flash the fault code To reset lockout conditions with SW2 8 On thermostat inputs Y1 Y2 and W must be removed for at least 3 seconds To...

Page 31: ...er G The blower will start immediately upon receiving a thermostat G command If there are no other commands from the thermostat the ECM will run on G speed until the G command is removed Regardless of...

Page 32: ...gs The AID Tool simply plugs into the exterior of the cabinet in the AID Tool port ABC Control Board Layout Aurora Base Control LED Displays These three LEDs display the status configuration and fault...

Page 33: ...ntrol will monitor water and refrigerant temperatures to determine if conditions are satisfactory for heating water LED1 red LED will flash code 15 when the DHW limit is reached and when conditions ar...

Page 34: ...ensor Smoke CO Alarm Fault no lockout info only Switch output from Smoke CO sensor Dirty Filter Alarm no lockout info only Output from dirty filter sensor Home Automation 2 E24 HA2 With a closed dry c...

Page 35: ...ange will be noticed from normal cooling Dehumidification mode will be shown on the ABC and the communicating thermostats Fault LED LED1 Red Red Fault LED LED Flash Code Lockout Reset Remove Fault Con...

Page 36: ...lable in five models with equipment rated fuses to provide additional circuit protection The fuses are panel mounted to allow easy inspection and removal without removing the cover on the disconnect C...

Page 37: ...ing setpoint must be set below room temperature 3 Be sure that the compressor and water control valve or loop pump s are activated 4 Verify that the water flow rate is correct by measuring the pressur...

Page 38: ...g performance based on entering air temperatures of 80 F DB 67 F WB Heating performance based on entering air temperature of 70 F DB Operating Limits F C F C Air Limits Min Ambient Air 45 7 2 45 7 2 R...

Page 39: ...x 500 485 for water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEATING CYCLE ANALYSIS...

Page 40: ...F 09 1 2 1 0 0 9 0 8 0 7 0 6 1 8 2 3 2 2 2 0 1 9 1 8 2 5 3 8 3 7 3 5 3 3 3 1 12 1 5 0 9 0 8 0 7 0 6 0 5 2 3 1 7 1 5 1 4 1 3 1 1 3 5 3 0 2 7 2 5 2 4 2 2 15 2 0 1 7 1 6 1 5 1 4 1 3 3 0 3 3 3 2 3 0 2 9 2...

Page 41: ...ressure Note On open loop systems if the installation is in an area with a known high mineral content 125 PPM or greater in the water it is best to establish with the owner a periodic maintenance sche...

Page 42: ...iption Date By All Updated Nomenclature and Wiring Schematics ABC Controls 1 Sept 2015 MA All Obsoleted PSC Option Updated Nomenclature Updated Wiring Schematics 04 Mar 2015 MA All Updated with All Al...

Page 43: ......

Page 44: ...mps Size 0 75 1 5 Tons Document Type Installation Manual Part Number IM1010CGB Release Date 09 15 2015 The manufacturer has a policy of continual product research and development and reserves the righ...

Reviews: