39
ASTON COMPACT INSTALLATION MANUAL
Controls - FX10 (optional) cont.
MUI Menu Navigation for Single Compressor - Aston Compact Series Water-to-Air
Welcome
Info Status Temps Outputs Settings Maint Alarms Alm-History
Water Source
Heat Pump
PROFXENV-XX
_/_/__
Info
Run Mode
Auto
Eff Occup’y
Occ
Y1 Input
OFF
Y2 Input
OFF
G Input
OFF
O Input Heat/Cool
Occ Input
Occ
Temp Occ Inp
OFF
Condensate NML
Emg Input
Run
Lo Press
ON
Hi Press
ON
Rndm Tmr
0
BI-4 Input
OFF
Status
Zone Temp
77.2 ºF
Dis Air Temp
51.0 ºF
Eff Clg Setpt
70.0°F
Eff Htg Setpt
66.0°F
Water Coil
77.8°F
Low WC Limit
30.0°F
Humidity 56.7
%RH
WarmCool AI
14.6
WarmCoolAdj
0.2
Temps
nvoFanStatus ON
CmpCmd Status
OFF
Cmp Capacity
OFF
Rev Valve
Heat
X1 Output
OFF
X2 Output
OFF
PWMOut 98%
BO5 OFF
BO9 OFF
AO2 Output
0%
Outputs
Settings
Unit of Measure
F
Occ Clg Setpt
73.9 ºF
Occ Htg Setpt
69.9 ºF
Unocc Clg
84.0 ºF
Unocc Htg
60.0 ºF
DeHumSetpt 0%
SensorSelect TAXXJ02
Maintenance
MinClgSetpt 60.0
ºF
MaxHtgSetpt 89.9 ºF
W Coil LoLim1 30.0 ºF
W Coil LoLim2 15.0 ºF
TmpOccTime 120 min
Rev Vlv Default Heating
BO5 Mode Network
CompStrtDly 90 sec
SpaceT Offset -1 ºF
DehumEnaDis Dis
Acc1 Action On Comp
Acc2 Action On Fan
SW1 OFF
SW2 OFF
SW3 ON
SW4 OFF
SW5 OFF
SW6 OFF
SW7 ON
SW8 OFF
SW9 OFF
SW10 ON
SW11 OFF
SW12 OFF
ECM
ALARM SUMMARY
^/High Pressure
Alarms
Press right arrow key
one time from
Maintenance Menu
No more than three
speeds should be “ON”
at one time
Alarm #Events
Condensate 0
Hi Pressure
0
Low Pressure
0
Low Temp
0
Bad Sensor
0
Alm-History
NOTE:
This FX10 application implements an
alarm history
which is reset
only by cycling power . This history shows on the Alm-History page. Any
alarm showing 4+ events has occurred more than 4 times.
Alarm lock-outs
are reset by cycling power, by pressing the “ESC” and
Return keys simultaneously for a minimum of 15 seconds, or by
commanding the nviAlarmReset over the BAS network.
Test mode
is enabled by holding the ‘Esc’ and Down Arrow simultaneously
for a minimum of 15 seconds and releasing. Test mode times out after 30
minutes, and may also be ended by pressing ‘ESC’ and Up Arrow
simultaneously and releasing . Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cycling
the reversing valve without compressor shutdown.