background image

Insulation of ducts in heated rooms

Genvex recommends the following:

Supply and extract ducts

In a warm attic, the supply and extract ducts must be provi-

ded with 50 mm of insulation finished with

aluminium foil.

Supply and extract ducts routed through heated rooms in 

the home need not be insulated unless

cooling, bypass or geothermal heat exchangers are used. In

such cases, the supply duct must be insulated. 

Fresh air and discharge ducts

In warm attics and heated rooms in the home, fresh air and 

discharge ducts must be provided with a minimum of 50 

mm of insulation. In addition, the insulation must be lined 

on the outside with plastic or aluminium foil to prevent con-

densation in the insulation.

Contact your local supplier for advice on national guide-

lines on insulation.

When using a geothermal heat exchanger, it is recommen-

ded adding 100 mm of insulation to the fresh air duct.

Post-heating of the supply air 

Since the countercurrent heat exchanger cannot recover all

the heat from the extract air to the supply air, in the winter 

season the supply air will be approx. 1–4°C lower than the 

room temperature in the home. If it is desired to use the 

system for heating, a water or electric heating surface able 

to heatthe supply air to room temperature can be installed.

Water post-heating surface

To protect the water post-heating surface against frost 

burst, a water frost sensor must be installed on the water 

post-heating surface and the water post-heating surface 

must be insulated. The water frost sensor is installed on the 

back of the slats of the water post-heating surface. The 

sensor for controlling the motor valve is installed in the 

supply duct approx. 500 mm after the water post-heating 

surface so that it is not affected by radiant heat from the 

heater. The water connection to the water post-heating 

surface must be executed by an authorised plumber.

Electric post-heating surface

The sensor for controlling the electric heating surface is 

installed in the supply duct approx. 500 mm after the 

electric heating surface so that it is not affected by radiant 

heat from the heater.

Electric preheater

At outdoor temperatures below 0°C, it is recommended 

installing an electric preheater to prevent ice accumulation 

in the countercurrent heat exchanger. The sensor for 

controlling the electric preheater must be installed in the 

fresh air duct 500 mm before the electric preheater (in the 

case of an on/off preheating surface).

Note – when a modulating preheating surface with a solid 

state relay is used, the existing fresh air temperature 

sensor in the ventilation unit can be used to control the 

preheater (no additional temperature sensor is required).

With a factory-fitted, integrated preheating surface, it is 

recommended using the built-in discharge temperature 

sensor as a reference sensor (see Optima 270 operating 

instructions for configuration).

Capacity

The diagram shows the temperature increase of the air for different air volumes after it has passed through the heating 

surface. To ensure as low an energy consumption as possible, the lowest possible power must be selected (this primarily 

applies to the on/off heating surface).

Temperature increase °C

Air volume m

3

/h

0

20

40

60

80

100

120

50

100

150

200

250

300

350

400

450

300 watt

600 watt

900 watt

1200 watt

1500 watt

1800 watt

8  

 

Summary of Contents for ECO 190 XL

Page 1: ...INSTALLATION MANUAL ECO 190 XL Mechanical ventilation with passive heat recovery A ...

Page 2: ...ts in heated rooms 8 Post heating of the supply air 8 Electrical Installation 9 Control and adjustment of the system 9 Optimal initial adjustment of the system 10 System maintenance 10 Trouble shooting 11 Optional equipmant for the ECO 190 XL ventilation unit 12 Spare parts 13 Electrical diagram OPT270 14 Declaration of conformity 15 Disassembly instructions 15 ...

Page 3: ...ived guidance on using the appliance in a safe way and under stand the dangers involved Children must not play with the appliance Cleaning and user maintenance must not be per formed by children without supervision Subject to change Labelling The CE label represents Genvex s assurance that the pro duct complies with all regulations imposed on the product in accordance with relevant EU directives T...

Page 4: ...nected to the right side of the ven tilation unit when the main control board of the machine is facing you Labels on the ventilation unit indicate how the ductwork is to be connected PLEASE NOTE that project specific models can be confi gured for left hand connection if this is the case the labels indicate how the ductwork should be connected On a right configured model the condensate drain and wa...

Page 5: ...2 Udsugningluft 3 Indblæsning 4 Modstrømsveks 5 Indblæsningsve 6 Udsugningsvent 7 Friskluftfilter 8 Udsugningsfilter 9 Eltilslutning 10 Kondensafløb 11 Bypass 12 Bypassklap 13 Forvarmer 14 IO Print 15 NJ45 Adapter 16 1 Fresh air 2 Discharge 3 Extract air 4 Supply air 5 Countercurrent exchanger 6 Supply air fan 7 Discharge air fan 8 Fresh air filter 9 Extract air filter 10 Electrical connection 11 ...

Page 6: ...at a sufficiently low level so that no noise is generated by the supply and extract fittings When positioning fresh air and discharge hoods grates ensure that the two air currents do not short circuit and thereby prevent the discharge air being sucked in again It is recommended that grates should be placed on the north or east side of the house to achieve optimal comfort in homes flats It is recom...

Page 7: ...tive pressure is created in the unit which means it is necessary to ensure that the water trap contains a water column of at least 50 mm Insulation of ducts in cold attics To benefit from the unit s high recovery potential efficiency the ducts must be correctly insulated Supply and extract ducts In order to minimise heat loss from the duct system in cold attics supply and extract ducts must be pro...

Page 8: ...s of the water post heating surface The sensor for controlling the motor valve is installed in the supply duct approx 500 mm after the water post heating surface so that it is not affected by radiant heat from the heater The water connection to the water post heating surface must be executed by an authorised plumber Electric post heating surface The sensor for controlling the electric heating surf...

Page 9: ...close they are to the unit 6 If a reheating surface is installed in the system the supply air temperature is set to 0 3 C below the room temperature in the home The system can now be put into operation and run until the system is adjusted using specialist ventilation measuring equip ment Electrical installation The electrical connection must be executed by an authori sed electrician See wiring dia...

Page 10: ...then rinse it e g in the bathroom using the shower head The heat exchanger plates must be handled carefully They have sharp edges and must not be damaged Fan Check the two fan wheels for dirt If they are dirty they can be cleaned with a brush bottle washer etc Supply and extract valves Clean the valves by wiping them with a dry cloth Make sure that the valve does not rotate and thus cause a change...

Page 11: ...l switch off The electric heating surface is equipped with a fire thermostat which automatically shuts off the power if the temperature exceeds 50 C When the temperature drops the heating surface automatically swit ches back on As extra security there is a built in thermal fuse which switches off if the temperature exceeds 100 C Reconnection must be performed manually This does not apply to PTC el...

Page 12: ... volume even at cold outdoor temperatures Condensate pump the ECO 190 XL can be supplied with a factory fitted condensate pump that makes it possible to divert condensate even in difficult conditions Note only recommended in combination with condensation level switch Condensation level switch must be connected to external start stop on the main circuit board for automatic shut off of the ventilati...

Page 13: ...69875 Optima 270 print 2 069820 XL Fan incl cabinet 3 069344 Exchanger GS18 x 460 alu 069345 Exchanger GS18 x 460 plastic 4 069370 Filter G4 Coarse 069371 Filter M5 ePM10 069372 Filter F7 ePM1 No Item no Description 5 069221 Packing list 6 069382 Base plate assembled 7 060536 Belimo motor CM230 FR 8 069761 Bypass flap large 9 069354 Cable entry 2 10 069365 Level switch complete ...

Page 14: ...Exhaust air Sensor T3 Outdoor air Sensor T1 Supply air Sensor T9 Option External stop EC fan Extract air Blue Yellow EC fan Supply air Blue Yellow EC fan Extract air 1x230V 50Hz Brown Brown Blue Blue Yellow green Humidity sensor P1 EC fan Supply air 1x230V 50Hz Belimo CM230 ON OFF Bypass 2x230V 50Hz White Control signal for Rotor Bypass Motorvalve Modulating Reheating Modulating Preheating Potenti...

Page 15: ...ve fan Remove condensation level switch Remove bypass actuator Remove heat exchanger DISASSEMBLY INSTRUCTIONS 15 DECLARATION OF CONFORMITY The declaration of conformity can be downloaded from www genvex com ...

Page 16: ...n society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All Genvex systems are rated with energy label A The original Genvex units are assembled by skilled and expe rienced technicians and have a lifetime that in many cases is measured in decades The units are approved by all applicable stan dards and are easy to operate and service Last but not least all Genv...

Reviews: