background image

10   

System maintenance

REMEMBER TO SWITCH OFF THE POWER BEFORE 

 OPENING  THE  UNIT.

Filters

When the filter timer reaches the set value for a filter 

replacement, this will appear in the text in the Optima 

Touch display or be indicated by a yellow, flashing light on 

the Optima Basic. This means that the filters must be 

replaced/cleaned.

The system is stopped at the system switch or the switch 

at the switchboard. The filter flaps are opened as indicated 

and the filters removed. When the filters have been 

cleaned/replaced, the front doors are closed and the filter 

alarm can now be reset. The system then returns to normal 

operation.

If you want to replace the filters with a different time 

interval, this can be done via the user menu.

Do not vacuum or clean at high air pressure. This will 

damage the filter!

Condensate drain

In connection with the filter replacement carried out before 

the autumn, check the condensate drain for any clogging 

with dirt, and check whether there is water in the water 

trap. The water trap cannot dry out because, due to the 

negative pressure of the unit, air will be sucked into the unit 

and the unit will not be able to get rid of the condensate.

Pour 1 litre of water into the condensate tray and see if it 

drains unhindered. If the condensate drain is not working, 

there is a risk of water damage to the home.

Countercurrent heat exchanger

Inspect the countercurrent heat exchanger. If it is dirty, 

take it out and wash it in warm soapy water and then rinse 

it, e.g. in the bathroom using the shower head.

The heat exchanger plates must be handled carefully.  

They have sharp edges and must not be damaged. 

Fan

Check the two fan wheels for dirt. If they are dirty, they can 

be cleaned with a brush, bottle washer, etc.

Supply and extract valves

Clean the valves by wiping them with a dry cloth. Make sure 

that the valve does not rotate and thus cause a change in 

the air volume.

Important:

  When reinstalling the front plate on the ventila-

tion unit, do not use power tools to tighten the bolts, as this 

may result in damage to the threaded connections. Careful-

ly tighten all the front-plate bolts until the plate is firmly 

seated on the cabinet of the ventilation unit.

Optimal initial adjustment of the system

Genvex recommends that the ventilation unit should be 

adjusted by an authorised Genvex dealer before commissi-

oning.

Before starting the initial adjustment, make sure that the 

six points in the section on inspection and initial adjust-

ment have been completed. Then start the unit:

Set the initial basic ventilation value, which is speed 2. To 

reduce energy consumption as much as possible, first 

adjust the main air volumes to the desired air volume by 

adjusting the speed of the fans via the control panel.

Then adjust the supply and extract valves with air measu-

ring equipment (during initial adjustment of the valves, 

remember to lock them and to rotate the baffle in the 

supply valves so that the air blows in the right direction).

Then check the main air volumes again and precisely adjust 

the main air volumes using the fresh air and extract air 

valves (remember to lock the valves in position after initial 

adjustment).

Summary of Contents for ECO 190 XL

Page 1: ...INSTALLATION MANUAL ECO 190 XL Mechanical ventilation with passive heat recovery A ...

Page 2: ...ts in heated rooms 8 Post heating of the supply air 8 Electrical Installation 9 Control and adjustment of the system 9 Optimal initial adjustment of the system 10 System maintenance 10 Trouble shooting 11 Optional equipmant for the ECO 190 XL ventilation unit 12 Spare parts 13 Electrical diagram OPT270 14 Declaration of conformity 15 Disassembly instructions 15 ...

Page 3: ...ived guidance on using the appliance in a safe way and under stand the dangers involved Children must not play with the appliance Cleaning and user maintenance must not be per formed by children without supervision Subject to change Labelling The CE label represents Genvex s assurance that the pro duct complies with all regulations imposed on the product in accordance with relevant EU directives T...

Page 4: ...nected to the right side of the ven tilation unit when the main control board of the machine is facing you Labels on the ventilation unit indicate how the ductwork is to be connected PLEASE NOTE that project specific models can be confi gured for left hand connection if this is the case the labels indicate how the ductwork should be connected On a right configured model the condensate drain and wa...

Page 5: ...2 Udsugningluft 3 Indblæsning 4 Modstrømsveks 5 Indblæsningsve 6 Udsugningsvent 7 Friskluftfilter 8 Udsugningsfilter 9 Eltilslutning 10 Kondensafløb 11 Bypass 12 Bypassklap 13 Forvarmer 14 IO Print 15 NJ45 Adapter 16 1 Fresh air 2 Discharge 3 Extract air 4 Supply air 5 Countercurrent exchanger 6 Supply air fan 7 Discharge air fan 8 Fresh air filter 9 Extract air filter 10 Electrical connection 11 ...

Page 6: ...at a sufficiently low level so that no noise is generated by the supply and extract fittings When positioning fresh air and discharge hoods grates ensure that the two air currents do not short circuit and thereby prevent the discharge air being sucked in again It is recommended that grates should be placed on the north or east side of the house to achieve optimal comfort in homes flats It is recom...

Page 7: ...tive pressure is created in the unit which means it is necessary to ensure that the water trap contains a water column of at least 50 mm Insulation of ducts in cold attics To benefit from the unit s high recovery potential efficiency the ducts must be correctly insulated Supply and extract ducts In order to minimise heat loss from the duct system in cold attics supply and extract ducts must be pro...

Page 8: ...s of the water post heating surface The sensor for controlling the motor valve is installed in the supply duct approx 500 mm after the water post heating surface so that it is not affected by radiant heat from the heater The water connection to the water post heating surface must be executed by an authorised plumber Electric post heating surface The sensor for controlling the electric heating surf...

Page 9: ...close they are to the unit 6 If a reheating surface is installed in the system the supply air temperature is set to 0 3 C below the room temperature in the home The system can now be put into operation and run until the system is adjusted using specialist ventilation measuring equip ment Electrical installation The electrical connection must be executed by an authori sed electrician See wiring dia...

Page 10: ...then rinse it e g in the bathroom using the shower head The heat exchanger plates must be handled carefully They have sharp edges and must not be damaged Fan Check the two fan wheels for dirt If they are dirty they can be cleaned with a brush bottle washer etc Supply and extract valves Clean the valves by wiping them with a dry cloth Make sure that the valve does not rotate and thus cause a change...

Page 11: ...l switch off The electric heating surface is equipped with a fire thermostat which automatically shuts off the power if the temperature exceeds 50 C When the temperature drops the heating surface automatically swit ches back on As extra security there is a built in thermal fuse which switches off if the temperature exceeds 100 C Reconnection must be performed manually This does not apply to PTC el...

Page 12: ... volume even at cold outdoor temperatures Condensate pump the ECO 190 XL can be supplied with a factory fitted condensate pump that makes it possible to divert condensate even in difficult conditions Note only recommended in combination with condensation level switch Condensation level switch must be connected to external start stop on the main circuit board for automatic shut off of the ventilati...

Page 13: ...69875 Optima 270 print 2 069820 XL Fan incl cabinet 3 069344 Exchanger GS18 x 460 alu 069345 Exchanger GS18 x 460 plastic 4 069370 Filter G4 Coarse 069371 Filter M5 ePM10 069372 Filter F7 ePM1 No Item no Description 5 069221 Packing list 6 069382 Base plate assembled 7 060536 Belimo motor CM230 FR 8 069761 Bypass flap large 9 069354 Cable entry 2 10 069365 Level switch complete ...

Page 14: ...Exhaust air Sensor T3 Outdoor air Sensor T1 Supply air Sensor T9 Option External stop EC fan Extract air Blue Yellow EC fan Supply air Blue Yellow EC fan Extract air 1x230V 50Hz Brown Brown Blue Blue Yellow green Humidity sensor P1 EC fan Supply air 1x230V 50Hz Belimo CM230 ON OFF Bypass 2x230V 50Hz White Control signal for Rotor Bypass Motorvalve Modulating Reheating Modulating Preheating Potenti...

Page 15: ...ve fan Remove condensation level switch Remove bypass actuator Remove heat exchanger DISASSEMBLY INSTRUCTIONS 15 DECLARATION OF CONFORMITY The declaration of conformity can be downloaded from www genvex com ...

Page 16: ...n society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All Genvex systems are rated with energy label A The original Genvex units are assembled by skilled and expe rienced technicians and have a lifetime that in many cases is measured in decades The units are approved by all applicable stan dards and are easy to operate and service Last but not least all Genv...

Reviews: