PROCESS DESCRIPTION
Gentherm Global Power Technologies
Page 21
Interface
Operation
Specs
SI1 - SCADA Start
input
Signal received from the SCADA system to request a
TEG start
5-36 Vin,
1-7mA
SI2 - SCADA Stop
input
Signal received from the SCADA system to request a
TEG stop
5-36 Vin,
1-7mA
SI3 - SCADA Reset
input
Signal received from the SCADA system to request a
reset of the Lockout state
5-36 Vin,
1-7mA
SI4 - SCADA Auto
input
Signal received from the SCADA system to change the
Auto Functionality On or Off
5-36 Vin,
1-7mA
SO1 - SCADA Run
output
Signal to the SCADA system that the TEG is running.
Blinks during startup
Up to 36V,
200mA
contact closure
SO2 - SCADA Fuel
output
Signal to the SCADA system that the fuel pressure
switch is closed, indicating fuel available
Up to 36V,
200mA
contact closure
SO3 - SCADA
Lockout output
Signal to the SCADA system that the SI System failed
to start
Up to 36V,
200mA
contact closure
SO4 - SCADA Auto
output
Signal to the SCADA system that the Auto functionality
is on
Up to 36V,
200mA
contact closure
SO5 - SCADA Local
output
Signal to the SCADA system that the TEG is operating
in the Local mode. SCADA start signals are ignored till
the mode timeout switches back to Remote
Up to 36V,
200mA
contact closure
S1 button - Start
Operator button to start the TEG
S2 button
–
Stop
Operator button to stop the TEG
S3 button
–
Reset
Operator button to reset the Lockout state
S4 button
–
Auto
Operator button to switch Auto functionality on or off
S5 button
–
Display
Operator button to turn on the display and toggle
through measured values
S6 button
–
Adjust
Operator button to toggle through the adjust- able
values. Up and Down buttons can be used to make
changes to adjustable values
S7 button
–
Up
Operator button for incrementing an adjustment
S8 button
–
Down
Operator button for decrementing an adjustment