Step 7: Re-Install panel cover, Verify proper operation of interlock. Main breaker
ON,
generator breaker
OFF
and generator breaker
CAN NOT
be turned on. Generator breaker
ON
, main breaker
OFF
and main breaker
CAN NOT
be turned on.
Generator on
Main on
Step 8: Place Generator start-up procedure label on panel box, Place CAUTION label on panel box and electric meter pan.
The MAIN and the GENERATOR breakers should NEVER be able to be turned on at the same time. If panel cover is removed the
Generator breaker is NEVER to be turned on. If for any reason the interlock does not function properly, DO NOT USE and contact us
immediately at
for support and instructions.
Thank You for your support,
GenInterlock Team
DISCLAIMER:
GenInterlock.com is NOT responsible for misuse or improper installation. All electrical
equipment should be installed and maintained by qualified personnel. Any consequences arising from improper
use is the responsibility of the user.