Sec-4.4
Section 4: Programming
Setting Travel Limits:
1. If operator is in RUN mode, press CAL/RUN key to enter CALIBRATION MODE.
2. Use the SCROLL Key to scroll through the menu until UP LIMIT > CLR is displayed.
3. Jog the door using the OPEN key until you reach the desired height.
4. Press SET/CLEAR key to switch display to UP LIMIT>SET . FIG. 5.
5. Press SCROLL DN key until display reads DOWN LIMIT CLR.
6. Jog door down to 2in. from floor. (See note below).
7. Press SET/CLR to switch display to DOWN LIMIT SET. FIG. 6.
8. Press SCROLL DN key until display reads LIMIT OVERRUN.
OPEN
CLOSE
STOP
CAL
RUN
SCROLL
SCROLL
SET
CLEAR
UP LIMIT SET
OPEN
CLOSE
STOP
CAL
RUN
SCROLL
SCROLL
SET
CLEAR
DOWN LIMIT SET
UP and/or DOWN
1. If operator is in RUN mode, press CAL/RUN to enter CALIBRATION MODE.
2. Press SCROLL until display reads UP LIMIT>SET or DOWN LIMIT>SET. FIG. 5.
3. Press SET/CLEAR to switch display to UP LIMIT>CLR or DOWN LIMIT>CLR.
4. Jog the door using the OPEN or CLOSE key until you reach the desired position.
5. Press SET/CLEAR to switch display to UP LIMIT>SET or DOWN LIMIT>SET.
6. Press CAL/RUN to return to run mode, or continue with LIMIT OVERRUN programming on the next page.
Resetting Travel Limits:
NOTE:
The recommended set-point for the DOWN travel limit is at approximately 2in. off the floor. This final
distance will be covered by the Limit Overrun Function to establish a more accurate seal.
FIG. 5
FIG. 6