25
-
-
Rem.sense
Local sense
Local sense
Rem.sense
+
+
Load lines, twisted pair,
shortest length possible.
+V
-V
Load#1
+
-
Load#3
+
-
Load#2
+
-
Power
Supply
Fig.3-13: Multiple loads connection, radial distribution, local sense
-
-
Rem.sense
Local sense
Local sense
Rem.sense
+
+
Distribution terminal
+V
+V
-V
-V
Load#1
+
-
Load#3
+
-
Load#2
+
-
Power
Supply
Fig.3-14: Multiple loads connection with distribution terminal
3.9.10 Multiple load connection with distribution terminals
If remotely located output distribution terminals are used, the power supply output terminals should
be connected to the distribution terminals by a pair of twisted and/or shielded wires. Each load
should be separately connected to the remote distribution terminals (see Fig.3-14).
If remote sensing is required, the sensing wires should be connected to the distribution terminals or
at the most critical load.
3.9.11 Grounding outputs
Either the positive or negative output terminals can be grounded. To avoid noise problems caused
by common-mode current flowing from the load to ground, it is recommended to ground the output
terminal as close as possible to the power supply chassis ground.
Always use two wires to connect the load to the power supply regardless of how the system is
grounded.
Models up to 60VDC Rated Output shall not float
outputs more than +/-60VDC above/below chassis
ground. Models > 60VDC Rated Output shall not float
outputs more than +/-600VDC above/below chassis
ground.
Bei Modellen bis 60V DC Nennausgangsspannung darf
der Potentialunterschied zwischen Ausgang und
Geh use-Erdung nicht mehr als +/-60V DC betragen.
Bei Modellen mit mehr als 60V DC
Nennausgangsspannung darf der Potentialunterschied
nicht mehr als+/-600V DC gegen ber der Geh use-
Erdung aufweisen.
�
�
�
WARNING
WARNUNG
25