47
F22 – Reverse Enable/Disable
Factory Setting: “000” [Enable Reverse Run] –
F22 is used to enable or disable
the drive from operating in the reverse direction. F22 is factory set to “000”
[Enable Reverse Run] which will allow the drive to be operated in the reverse
direction.
Note:
If F22 is set to “001” [Disable Reverse Run], F04 [Motor Direction] can only
be programmed to “000” [Forward Direction].
F23 – Auto Restart After a Fault has Cleared
Factory Setting: “000” [Enable Auto Restart] –
F23 is used to enable or disable
automatically restarting the drive after a momentary power loss (not exceeding 2
seconds). F23 is factory set to “000” [Enable Auto Restart], which will automati-
cally restart the drive after a momentary power loss. To set the drive for manual
restart, after a momentary power loss, set F23 to “001” [Disable Auto Restart].
Note:
If the power loss time does not exceed 2 seconds, Auto Restart will occur.
If the power loss time exceeds 2 seconds, Auto Restart will be attempted only if
F24 [Number of Auto Restart Attempts] is set to “001” - “005”.
F24 – Number of Auto Restart Attempts
Factory Setting: “000” [Zero Auto Restart Attempts] –
F24 is used to set the
number of Auto Restart Attempts that will be performed after a fault has cleared.
F24 is factory set to “000” [Zero Auto Restart Attempts], which will not allow the
drive to automatically restart after a fault has cleared.
Programmable Range: 0 - 5 Auto Restart Attempts
F21 Setting
Output Relay Contacts
Power
Off
Drive In
Stop Mode
Drive In
Run Mode
Frequency
Reached
Fault
001 [Run]
Open
Open
Closed
—
—
002 [Frequency Reached]
Open
Open
—
Closed
—
003 [Fault]
Open
Open
—
—
Closed
TABLE 16 – MULTIFUNCTION OUTPUT RELAY OPERATING MODES
F22 = 000:
Enable Reverse Run
001:
Disable Reverse Run
F23 = 000:
Enable Auto Restart (see note below)
001:
Disable Auto Restart
Sec. IX – Programmable Functions (Detailed) (Cont.)