Syntax for switching of the outputs
Set the RCCMD client at port 6002 to “on” and restart it. Install the RCCMD Windows Wizard and
open a DOS box. The following is a syntax example with the IP address 192.168.202.165:
C:\RCCMD\
rccmd -s -a 192.168.222.238 -p 6002 -se "EXECUTE |UPSCMD|20000|1,1"
ATTENTION! The blank after the “Execute” is important!
Common syntax for the switching of the outputs of the SiteManager:
|UPSCMD|20000|1,0 output 1 to low
|UPSCMD|20000|1,1 output 1 to high
|UPSCMD|20000|2,0 output 2 to low
|UPSCMD|20000|2,1 output 2 to high
|UPSCMD|20000|3,0 output 3 to low
|UPSCMD|20000|3,1 output 3 to high
|UPSCMD|20000|4,0 output 4 to low
|UPSCMD|20000|4,1 output 4 to high
|UPSCMD|20000|5,0 output 5 to low
|UPSCMD|20000|5,1 output 5 to high
|UPSCMD|20000|6,0 output 6 to low
|UPSCMD|20000|6,1 output 6 to high
|UPSCMD|20000|7,0 output 7 to low
|UPSCMD|20000|7,1 output 7 to high
|UPSCMD|20000|8,0 output 8 to low
|UPSCMD|20000|8,1 output 8 to high