Figure 33:
HTTP - Event Editor
The Event Editor allows you to edit, delete and test existing events, as well as to add a new event job.
Just click on the desired action to enter the Job Editor, who lets you make the configuration.
4.4.1
Events
…
Please call the menu “Events / Alarms” in the Web-browser to open the main configuration site,
whereon all configurable events are listed.
4.4.1.1
… concerning the UPS
In the Sitemanager’s menu “Event overview” you see on top a couple of events concerning the state of
an connected UPS (usually numbered from 1). Which events are actual available depends on
connected UPS model. In the following, we introduce the main and important events which should be
handled in general, if a UPS is connected to the Sitemanager.
Powerfail
The event “Powerfail” will be released when the UPS has lost the power supply. This event is usually
used to proceed operations like backup-strategies, batch-files to be executed on client stations etc. pp.
You can configure such jobs with th
e “Remaining time”-parameter to ensure the actions will be
executed completely.
System shutdown
The event “system shutdown” will be released, if the configured “System Shutdown Time” (in the menu
“UPS model and system”) is reached. This means, there are yet the configured minutes left until the
battery’s capacity is expected to be finished (as calculated by the adapter).
This event should only be used to proceed all operations concerning your forced shutdown scenarios.
Further operations are usually configur
ed on the event “Powerfail”.
Note: This EVENT is the final task a CS121 can initiate before the UPS switches off! DO
NOT use this event for triggering shutdowns via RCCMD etc. because the remaining
time in this status is not secure. We strongly recomme
nd to use the event “Powerfail”
and configure the RCCMD shutdown calls with a UPS “remaining time”, this is the
best way to send RCCMD shutdowns to several IP-addresses in a certain logic or
sequence!
Battery low
The event “Battery low” will be released from the UPS when the battery charge has reached a critical
state.
UPSMAN started