Generac Power Systems RTSJ200A3 Owner'S Manual Download Page 7

 

 

5

If ALUMINUM conductors are used, apply corrosion inhibitor to 

conductors. Tighten terminal lugs to the torque values as noted on 

the "Utility Service Disconnect Circuit Breaker", and on the decal 

located on the inside of the door. After tightening terminal lugs, 

carefully wipe away any excess corrosion inhibitor.



 Use a torque wrench to tighten the conduc-

tors, being sure not to overtighten, or dam-

age to the insulating base could occur. If not 

tightened enough, a loose connection would 

result, causing excess heat which could 

damage the switch base.

Connect power source load conductors to clearly marked transfer 

mechanism terminal lugs as follows
1.  Connect UTILITY (NORMAL) power source cables to the top 

of the UTILITY SERVICE DISCONNECT circuit breaker.

2.  Connect GENERATOR (STANDBY) source power cables to 

ATS GENERATOR supply terminals, E1-E2.

3.  Connect non-essential customer LOAD leads to LSS switch 

terminals E1, E2.

4.  Connect critical customer loads to the circuit breakers on the 

load center provided.

Conductors must be properly supported, of approved insulative 

qualities, protected by approved conduit, and of the correct wire 

gauge size in accordance with applicable codes.
Be sure to maintain proper electrical clearance between live metal 

parts and grounded metal. Allow at least 1/2 inch for 100-400 

amp circuits.

2.5 NEUTRAL 

CONNECTIONS

The main neutral block is provided for the connection of the 

neutral (ungrounded conductors) of the Utility, Generator and non-

essential load neutrals. Tighten all wires to the specified torque. 

Torque values are given on the information decal located on the 

inside cover.
The main neutral block is connected (bonded) to the enclosure 

metal by a busbar. If bonding of the neutral is not necessary, the 

jumper can be removed. When the jumper bar is removed the 

control wires should be connected as follows:
•  #00 wire to the neutral block.
•  GRD wire to the enclosure.
The essential load neutrals are to be connected on the busbars 

mounted on the load center, next to the branch circuit breakers.

2.6  

CONNECTING CONTROL 
WIRES

Control system interconnections consist of N1, N2 and T1; and 

leads 0, 15B/194 and 23. The control and power leads must be 

routed in separate conduits. Recommended control wire gauge 

sizes for this wiring depends on the length of the wire, as recom-

mended in the following chart:

MAXIMUM WIRE LENGTH

RECOMMENDED WIRE 

SIZE

1-115 ft  (1-35m)

No. 18 AWG.

116-185 ft  (36-56m)

No. 16 AWG.

186-295 ft  (57-89m)

No. 14 AWG.

296-460 ft  (90-140m) 

No. 12 AWG.

3.1  

FUNCTIONAL TESTS AND
ADJUSTMENTS

Following transfer switch installation and interconnection, 

inspect the entire installation carefully. A competent, qualified 

electrician should inspect it. The installation should comply 

strictly with all applicable codes, standards, and regulations. 

When absolutely certain the installation is proper and correct, 

complete a functional test of the system.



 Perform functional tests in the exact order 

presented in this manual, or damage could 

be done to the switch.

IMPORTANT: Before proceeding with functional tests, read and 

make sure all instructions and information in this section are 

understood. Also read the information and instructions of labels 

and decals affixed to the switch. Note any options or accessories 

that might be installed and review their operation.

3.2   MANUAL OPERATION



 Do NOT manually transfer under load. 

Disconnect transfer switch from all power 

sources by approved means, such as the 

main circuit breaker(s).

3.2.1   ATS MANUAL OPERATION

A manual HANDLE is shipped with the transfer switch. Manual 

operation must be checked BEFORE the transfer switch is oper-

ated electrically. To check manual operation, proceed as follows 

(Figure 3.1):
1.  Turn the generator’s AUTO/OFF/MANUAL switch to OFF.
2.  Turn OFF UTILITY SERVICE DISCONNECT circuit breaker.
3.  Note position of transfer mechanism main contacts by 

observing the moveable contact carrier arm. This can be 

viewed through the long narrow slot in the inside cover of the 

ATS. The top of the moveable contact carrier arm is yellow to 

be easily identified.

Operation

Summary of Contents for RTSJ200A3

Page 1: ...This manual should remain with the unit Owner s Manual LTS Load Shed Switch...

Page 2: ...infor mation on tags decals and labels that may be affixed to the transfer switch Replace any decal or label that is no longer legible DANGER Connection of a generator to an electrical system normall...

Page 3: ...hazardous and possibly LETHAL electric shock DO NOT WORK ON THE TRANSFER SWITCH UNTIL ALL POWER VOLTAGE SUPPLIES TO THE SWITCH HAVE BEEN POSITIVELY TURNED OFF Competent qualified personnel should inst...

Page 4: ...will operate and disconnect the non essential loads which results in a reduction in the load on the generator The third function is a 16 circuit load center to connect the criti cal loads to These lo...

Page 5: ...switches 1 4 For one shot operation mode set DIP switch 5 to ON Reconnection of the non essential loads will occur one time after the time set on DIP switches 1 4 If DIP switch 5 is OFF the LSC will a...

Page 6: ...stalling Do not drop the switch Protect the switch against impact at all times and against construction grit and metal chips Never install a transfer switch that has been damaged This transfer switch...

Page 7: ...rals are to be connected on the busbars mounted on the load center next to the branch circuit breakers 2 6 CONNECTING CONTROL WIRES Control system interconnections consist of N1 N2 and T1 and leads 0...

Page 8: ...L position no further action is required If the handle is DOWN proceed with Step 1 Step 1 With the handle inserted into the moveable contact carrier arm move handle UP Be sure to hold on to the handle...

Page 9: ...NOW BEING DELIVERED TO TRANSFER SWITCH TERMINALS CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY DANGEROUS AND POSSIBLY FATAL ELECTRICAL SHOCK 7 With an accurate AC voltmeter and frequency meter chec...

Page 10: ...ual Operation Handle and operating lever of transfer switch should be in UP position 10 Turn on the UTILITY power supply to transfer switch using the UTILITY SERVICE DISCONNECT circuit breaker The uti...

Page 11: ...9 Notes...

Page 12: ...10 Notes...

Page 13: ...11 Notes...

Page 14: ...12 Installation Diagram 200 Amp Enclosure Drawing 0G8775 B...

Page 15: ...8 9 B 2 1 3 9 8 7 B D1 A 6 3 4 5 2 1 7 6 3 2 1 4 5 1 2 2 1 3 1 2 3 4 5 6 J4 RL2 D2 1 2 2 1 3 TO LOADS NON ESSENTIAL TOP TERMINALS TO GROUNDING ELECTRODE 194 OPTIONAL ALARM CONTACT CUSTOMER SUPPLIED N...

Page 16: ...Part No 0H8807 Revision E 08 01 13 Printed in U S A...

Reviews: